This appendix contains system specifications for all models of the IGX node.
This section provides general system information on the IGX 8410.
| System Capacity: | 1 shelf with 8 card slots. Has 2 dedicated front slots for NPMs. Has 2 dedicated back slots for SCMs (1 slot with blank plate). Up to 48 physical lines for UNI or NNI. Up to 8 physical lines for trunks. |
| Enclosure Size: | IGX 8410 Standalone/Rackmount: Height: 25 ins. (63.5 cm) standalone; 24.5 ins. (62.3 cm), rack Width: 19.9 ins. (50.5 cm), standalone; 19 ins. (48.3 cm.), rack Depth: 26.5 ins. (67.3 cm), standalone and rack-mount |
| Shipping Weight: | 270 pounds (122.7 kilograms) |
| Clearance Requirement: | Min. clearance: 30 inches front; nominal 30 ins. rear; 12 ins. side. |
| Power Input Voltage: | AC system: Normal operating range is 100-240 VAC, 47 to 63 Hz. The (under and over-voltage limits are 90-264 VAC). DC system: -42 to -56 VDC. Each AC supply can provide up to 400 watts to the card shelves. Space is available for 4 power supplies. |
| Input AC Power Connector: | IEC 16 Amp input connector. Six different power cords are available to comply with the standards of individual countries. Power cords are 6 feet (about 2 meters) long. See appendix titled Cabling Summary in the Cisco IGX 8400 Series Installation publication for details. |
| Current Requirements: | Configuration-dependent: use Network Design Tool for exact requirements. For planning purposes, use the following: |
| · AC System | 10 Amps maximum for 110 VAC, 5 A for 220 VAC. |
| · DC System | 20 Amps maximum at -48 VDC; 25 Amps at -42 VDC (worst case). |
| DC Input Connections: | 3-wire pluggable terminal block with screw terminal connectors. |
| Operating Environment: | 0× to 40× C (32× to 104× F) normal operation (50× C up to 72 hours). Maximum 85% relative humidity. |
| Shock: | Withstands 10 G, 10 ms. at 1/2 sine wave. |
| Vibration: | Withstands 1/4 G, 20-500 Hz. |
| Heat Transfer to Room: | IGX 8410: 2720 BTUs max. |
| System Capacity: | 1 or 2 shelves, each with 16 card slots. Requires 1 or 2 dedicated front slot(s) for NPMs. Requires 1 dedicated back slot for SCM. Up to 48 physical lines for UNI or NNI. Up to 16 physical lines trunks. |
| Enclosure Size: | IGX 8420 Standalone/Rackmount: HT: 32.25 ins. (82 cm.), standalone; 31.75 ins. (80.7 cm.), rack WD: 19.9 inches (50.5 cm), standalone; 19 inches (48.3 cm.), rack DP: 26.75 inches (68 cm), standalone; 26 inches (66 cm.), rack IGX 8430 Standalone/Rackmount: |
| Shipping Weight: | 600 pounds (270 kilograms) for a fully loaded IGX 8430 enclosure. 400 pounds (180 kilograms) for a fully loaded IGX 8420 enclosure. |
| Clearance Requirement: | Min. 30 inches front and rear; nominal 12-inch side clearance. |
| Power Input Voltage: | AC system: Normal operating range is 200-240 VAC, 47 to 63 Hz. The under and over-voltage range is 180-264 VAC. DC system: -42 to -56 VDC. Each AC supply can provide up to 875 watts to a card shelf. Cabinet has space for 6 AC power supplies. |
| Current Requirements: | Configuration-dependent: use Network Design Tool for exact requirements. For planning purposes, use the following: |
| · AC System | IGX 8420 or IGX 8430 node: 12 Amps at a nominal voltage of 200 VAC. At the under-voltage limit of 180 VAC, the current draw is 16 Amps max. |
| · DC System | IGX 8420 node: 24 Amps max. per circuit at -42 VDC (worst case) IGX 8430 node: 44 Amps at nominal -48 VDC; 50 Amps at -42 VDC maximum per circuit at -42 VDC. |
| Input AC Power Connector: | AC Power Distribution unit is the same for all cabinets: IEC 16 Amp input connector. Six different power cords available, depending on country of destination. See appendix titled "Cabling Summary," In the Cisco IGX 8400 Series Installation publication |
| DC Input Connections: | DC power is the same for all IGX 8420 or IGX 8430 cabinets shipped. DC: 3-screw pluggable terminal connectors. |
| Operating Environment: | 0× to 40× C (32× F to 104× F) normal operation (50× C or 122× F up to 72 hours). Maximum 85% relative humidity. |
| Shock: | Withstands 10 G, 10 ms. at 1/2 sine wave. |
| Vibration: | Withstands 1/4 G, 20-500 Hz. |
| Heat Transfer to Room: | IGX 8420: 4300 BTUs max, AC-powered system. 3600 BTUs in a DC-powered unit. IGX 8430: 8600 BTUs max, AC-powered system. 6800 BTUs in a DC-powered unit. |
| Voice Channel Interface: | 24-channel T1 (D4 format). 24-channel T1-ESF. 30-channel framed CEPT E1. |
| Voice Compression: | 32/24/16 Kbps ADPCM on the CVM 32/24/16 Kbps ADPCM 16 Kbps LDCELP (UVM only) Voice Activity Detection (VAD) compression |
| Compression Algorithm: | ITU-T G.721, G.723, G.726. Cisco 32 Kbps ADPCM Cisco LDCELP |
| PCM Encoding Types: | Accommodates m-Law or A-Law encoding, End-to-end conversion available. |
| Channel Gain Control: | -8 dB to +6 dB. |
| Signalling Modes: | T1: Robbed bit or CCS (ISDN). E1 and J1: Channel Associative Signalling (CAS) or Common Channel Signalling (CCS). |
| Signalling Conditioning: | Various make-busy and forced-idle routines during circuit alarm, configurable on a per-channel basis. |
| Quantizing Distortion Added: | 2.5 Quantizing Distortion Units (QDU)s with 32 Kbps ADPCM over 1 hop plus 0.7 QDUs with Digital Loss PAD (m-law or A-Law). |
| Nominal Transmission Loss: | 0 dB at 1 Khz. |
| Sync. Data Interfaces: | EIA/TIA-232C/D, EIA/TIA-449/422, V.24, X.21, and V.35 with IGX switch as DCE or DTE. |
| High-Speed Data Rates (HDM): | 2.4 Kbps to 1.344 Mbps. |
| Low-Speed Data Rates: | 2.4 to 19.2 Kbps per LDM port. |
| Ports per card: | LDI: 4 or 8. SDI: 4. |
| Control Leads Supported: | SDI: Per interface standards. SDI: Up to 7 in each direction for fast EIA. LDI: 3 in each direction for DCE and DTE for each port. |
| Control Lead Sync w/Data: | Control leads are sampled every 50 ms. A change normally follows data within 100 to 1000 msec. Fast EIA lead is within 1 byte. |
| Data Clocking: | Synchronous and isochronous clocking. Normal, looped, and split clock configurations. |
| Pleisochronous Clock Range: | ± 2 percent of nominal data rate. |
| Line Rate: | 1.544 Mbps, ± 50 bps (± 200 bps VCO lock range). |
| Line Code: | Bipolar AMI or B8ZS. |
| Framing Formats: | Fractional T1, adjacent or alternating channels. Minimum of four DS0 channels required. |
| Signal Level: | DSX-1 compatible. |
| Line Impedance: | Terminated=100 Ohms nominal. Bridged=1 KOhm. |
| Pulse Amplitude | Individual pulse amplitude 2.4 V-3.6 V (making a total base-to-peak amplitude of 6 V ± 0.6V) |
| Minimum Pulse Density: | Zero code suppression, either LSB, MSB or B8ZS. |
| Frame Format: | D4 and Extended Superframe (ESF). |
| VF Signalling: | Robbed bit D4 with A and B bits. |
| Max. Line Lengths: | Up to 533 feet with equalizers using ABAM cable. |
| Jitter Transfer: | Meets AT&T PUB 62411 specifications. |
| Jitter Tolerance: | Meets ANSI standards and AT&T PUB 62411 specs. |
| Connector: | DB 15 female. |
The following applies to each individual T1 line on the UFI-8T1:
| Line Rate: | 1.544 Mbps, ± 50 bps (± 200 bps VCO lock range). |
| Line Framing: | ESF per AT&T TR 54016. |
| Frame Relay Interface: | Meets ANSI T1.618, two-octet header. |
| Frame Relay Interface Rates: | Either 56 Kbps or n x 64 Kbps, where 1<=n<=24. Sum of all n<=24. |
| Number of Frame Relay Interfaces: | 1-24 occupied channels where 1<= n<= 24, and the sum of all n<=24. |
| Synchronization: | Transmitter can be either loop-timed to receiver or synchronized to shelf (normal mode). |
| Line Code: | Bipolar AMI or B8ZS. |
| Framing Formats: | Fractional T1, contiguous DS0s/timeslots. Minimum of four DS0 channels required. |
| Signal Level: | DSX-1 compatible. |
| Line Impedance: | Terminated=100 Ohms nominal. Bridged=1 KOhm. |
| Pulse Amplitude: | Individual pulse amplitude 2.4 V-3.6 V (making a total base-to-peak amplitude of 6 V ± 0.6V). |
| Minimum Pulse Density: | Zero code suppression, either LSB, MSB or B8ZS. |
| VF Signalling: | Robbed bit D4 with A and B bits. |
| Max. Line Lengths: | Up to 533 feet with equalizers using ABAM cable. |
| Input Jitter Tolerance: | Meets AT&T PUB 62411 specifications. |
| Output Jitter Tolerance: | Meets AT&T PUB 62411 specifications using normal mode synchronization. |
| Connector: | DB 15 female. |
| Line Rate: | 2.048 Mbps, ± 50 ppm (± 200 bps VCO lock range) |
| Line Code: | Bipolar AMI or HDB3 |
| Line Impedance: | 120 Ohms (balanced) or 75 Ohms (balanced or unbalanced) |
| Minimum Pulse Density: | Zero code suppression via HDB3 coding |
| Frame Format: | Unframed, 32-channel (G.703). Framed: 30 or 31-channel CEPT multiframe per ITU-T G.704. |
| VF Signalling: | CAS or CCS |
| Max. Line Lengths: | 100 meters. The E1 output complies with G.703, so cabling must not exceed -6dB/1000 feet at 1024 kHz (applies to 75-Ohm coax or 120-Ohm twisted pair up to 350 meters or 1000 feet). Cisco supplies cable with a maximum attenuation of 7 dB /1000 ft., but the maximum cable length for this E1 interface is 100 meters. |
| Jitter: | Transmit output jitter, receive jitter tolerance, and jitter gain meet G.823. |
| Electrical Interface: | Complies with G.703 Specification. |
| Connector: | DB 15 female or BNC. |
The following applies to each individual E1 line on the UFI-8E1:
| Line Interface Connector: | DB15 (120 Ohms), BNC (75 Ohms) |
| Line Rate: | 2.048 Mbps, ±50 bps (±200 bps VCO lock range). |
| Frame Relay Interface: | Meets ANSI T1.618, two-octet header. |
| Number of Frame Relay Interfaces: | 1-31 occupied channels where 1 <= n <= 31, and the sum of all n <= 31 |
| Frame Relay Interface Rate: | Either 56 Kbps or n x 64 Kbps, where 1 <= n <= 31. Sum of all n <= 31. |
| Line Code: | Bipolar AMI or HDB3. |
| Line Impedance: | 120 ohms (balanced) or 75 ohms, balanced or unbalanced. |
| Minimum Pulse Density: | Zero code suppression via HDB3 coding. |
| Frame Format: | Unframed, 32-channel (G.703). Framed: 30 or 31-channel CEPT multiframe per ITU-T G.704. |
| VF Signalling: | CAS or CCS. |
| Max. Line Lengths: | E1 output complies with G.703, so cabling must not exceed -6dB/1000 feet at 1024 kHz (applies to 75-ohm coax or 120-ohm twisted pair up to 350 meters or 1000 feet). |
| Input Jitter Tolerance: | Meets G.823. |
| Output Jitter Tolerance: | Meets G.823. |
| Electrical Interface: | Complies with G.703 Specification. |
| Connector: | Back card has either all DB15 female or all BNC connectors. |
| Required Hardware: | AIT front card on the IPX, BTM front card on the IGX. The back card is the AIT-E2 |
| Line Rate: | 8.448 Mbps |
| Line Coding: | HDB3. |
| Cell Delineation: | HEC |
| Physical Medium; | Coaxial |
| Line Length: | 50 feet maximum; 6 feet nominal |
| Connector: | BNC, 75 Ohms. |
| Synchronization: | Master/slave (NOTE: loop timing to IPX or IGX node is allowed.) |
| Interfaces per card: | One |
| Applicable Standards: | E2 specification and G.703. |
| Required Hardware: | AIT front card on the IPX or BTM front card on the IGX node. The back card is the AIT-HSSI. |
| Line Rate: | Presettable, programmable for the range 4-50.84 Mbps: increments depend on the attached DSU. |
| Line Coding: | NRZ. |
| Cell Delineation: | PLCP |
| Physical Medium: | Multi-conductor, 25 twisted pairs in a ribbon cable, 110 Ohms. |
| Line Length: | 50 feet maximum; 6 feet nominal |
| Connector: | 50-pin, 50 mil SCSI type. |
| Synchronization: | None--accepts DSU clocks |
| Interfaces per card: | Single port. |
| Applicable Standards: | High Speed Serial Interface specification, March, 1990 I.432, G.804. |
| Line Rate: | 2.048 Mbps, ± 50 ppm (± 200 bps VCO lock range) |
| Line Code: | Bipolar CMI |
| Line Impedance: | 120 Ohms (balanced) |
| Frame Format: | Per JJ-20.11 |
| VF Signalling: | CAS or CCS |
| Max. Line Lengths: | 100 meters. Cisco supplies cable with a maximum attenuation of 7 dB /1000 ft., but the maximum cable length recommended for this J1 interface is 100 meters. |
| Jitter: | Transmit output jitter, receive jitter tolerance, and jitter gain meet G.823. |
| Electrical Interface: | Complies with G.703 Specification. |
| Connector: | Two DB 15, female. |
| Line Rate: | 2.048 Mbps, ± 50 ppm (± 200 bps VCO lock range) |
| Line Code: | Bipolar CMI |
| Line Impedance: | 120 Ohms (balanced) or 75 Ohms (balanced or unbalanced) |
| Frame Format: | Per JJ-20.11 |
| VF Signalling: | CAS or CCS |
| Max. Line Lengths: | 100 meters. Cisco supplies cable with a maximum attenuation of 7 dB /1000 ft., but the maximum cable length recommended for this J1 interface is 100 meters. |
| Jitter: | Transmit output jitter, receive jitter tolerance, and jitter gain meet G.823. |
| Electrical Interface: | Complies with G.703 Specification. |
| Connector: | DB 15 female or BNC. |
| Type of Service: | Permanent Virtual Circuit (PVC). |
| Data Interface: | Per ITU-T I.122 and ANSI T1/S1 Standards. |
| Data Transfer Protocol: | LAP-D frame level core functions. |
| Input Data Format: | High Level Data Link (HDLC) protocol. |
| Input Data Frame Length: | Up to 4096 bytes. |
| Frame Integrity Check: | Frame Check Sequence and CRC check of data frame. If CRC fails, data frame is discarded at receiving node. |
| Input Data Rate: | 56 Kbps-2.048 Mbps. The maximum rate is available with only one of four ports on the back card active). |
| Ports per Card: | 4 Model D
31 Model E |
| PVCs per Port: | 252 per FRM card, distributed in any combination. |
| Port Electrical Interface: | ITU-T V.35. IGX and X.21 can act as a DCE or DTE for direction of control leads and timing on Model D and E using E1 or T1. |
| Data Clocking: | Normal or looped. |
| Virtual Circuit Identifier: | Data Link Connection Identifier (DLCI). |
| Control Protocol: | Local Management Interface with XON/XOFF type flow control. The IGX node sets FECN and BECN bits in frame relay frame. |
| Bundled Connections: | 252 virtual circuits per card 1024 virtual circuits per node. |
| Billing Time Accuracy: | Upon request from a user-device, the IGX node provides GMT from any node accurate to within 1 second. |
| Type of Service: | Permanent Virtual Circuit (PVC) |
| Interface Types: | User-to-Network (UNI) and Network-to-Network (NNI) per ITU I.361 and I.363 |
| Data Rates: | T1, E1, T3, E3 |
| ATM Layer: | Physical Layer Convergence Protocol per AT&T publication TA-TSY-00772 and 000773 for T3; ITU I-361 with HEC for E3 |
| Cell Rate: | 96,000 cells/sec. for T3, 80,000 cells/sec. for E3 |
| Adaptation Layer: | AAL5 |
| Number of PVCs per card: | 255 |
| VPI Addressing Range: | 0-255 |
| VCI Addressing Range: | 0-65535 |
| Traffic Queues: | CBR, VBR, and ABR |
| Management Protocol: | Layer Management Interface (LMI) and Interim Layer Management Interface (ILMI) |
| External Clock Sources: | The IGX switch synchronizes to the nearest, highest-stratm clock available. Any T1, E1, T3, E3 line, trunk, or optional external clock input can serve a clock source. |
| Internal to Node Source: | T1: 1.544 MHz, ± 10 ppm. (Stratum 4). E1: 2.048 MHz, ± 10 ppm (Stratum 4). |
| Clocking Hierarchy: | Dynamic primary, secondary, and tertiary clocking. |
| Network Control Terminal: | StrataView Plus workstation and software required for graphical display of network status, statistics gathering and display, and automatic downloading of software. |
| Control Terminal: | DEC VT100, WYSE 85, Televideo 970 or equivalent terminal for basic system configuring and alarm monitoring. |
| Remote Alarm Reporting: | Auto-dial modem connects to one of two control ports on each IGX node for automatic reporting of network alarms. |
| Remote Diagnostics: | Auto-answer modem connects to one of two control ports on each IGX node for remote diagnostic access by Cisco TAC or other authorized personnel. |
| Network Control Ports: | Two ports per node, (one EIA/TIA 232C interface and one Ethernet LAN port). |
| Alarm Notification: | Status of all trunks and nodes in network distributed to and stored by each individual node. Reported to StrataView Plus workstation at connecting node. |
| External Alarms: | Meets Bellcore Compatibility Bulletin #143 and AT&T Technical Reference PUB 43801 DS1 (T1) facility alarm requirements when equipped with DTI group. |
| Indicators and Controls: | Active and Fail lights on all cards and power supplies. |
|
|