|
|
![]() |
Warning Before you install, operate, or service the system, read the Site Preparation and Safety Guide. This guide contains important safety information you should know before working with the system. |
This chapter describes how to prepare your site for the installation of the switch and contains these sections:
![]() |
Note A site-planning checklist is provided in the "Site-Planning Checklist" section to help ensure that you complete all site planning activities before you install the switch. |
![]() |
Note Catalyst 4003 switches have two slots for removable AC-input power supplies. Catalyst 4006 switches have three slots for removable AC-input power supplies. Each power supply requires a separate power circuit. |
This section provides site power requirements and heat dissipation specifications for the Catalyst 4003 and 4006 switches. You should verify site power before you install the switch.
![]() |
Note Refer to the Site Preparation and Safety Guide for site power requirements, preinstallation requirements, and EMI recommendations. |
Knowing the power requirements is useful for planning the power distribution system necessary to support the switches. The heat dissipation specifications are an important consideration when estimating the air-conditioning requirements for an installation. Table 2-1 provides the power requirement and heat dissipation specifications for the Catalyst 4003 and 4006 switches, supervisor engines, and switching modules.
| Model Number/ Module Type | AC-Input Power (Watts) | DC-Output Power (Watts) | Heat Dis-sipation (BTU/HR) | Input Current at 90 VAC (Amps) | Input Current at 120 VAC (Amps) | Input Current at 180 VAC (Amps) | Input Current at 240 VAC (Amps) |
|---|---|---|---|---|---|---|---|
Catalyst 4003 chassis (with fans) | 12 | 9 | 41 | 0.13 | 0.10 | 0.07 | 0.05 |
Catalyst 4006 chassis (with fans) | 38 | 28 | 130 | 0.41 | 0.32 | 0.22 | 0.16 |
Catalyst 4003 supervisor engine (WS-X4012) | 59 | 46 | 201 | 0.65 | 0.49 | 0.33 | 0.25 |
Catalyst 4006 supervisor engine (WS-X4013) | 130 | 101 | 443 | 1.43 | 1.08 | 0.73 | 0.55 |
WS-X4306-GB | 19 | 15 | 65 | 0.21 | 0.16 | 0.11 | 0.11 |
WS-X4232-GB-RJ | 55 | 43 | 188 | 0.61 | 0.46 | 0.31 | 0.23 |
WS-X4232-RJ-XX | 109 | 85 | 371 | 1.20 | 0.90 | .61 | 0.46 |
WS-X4418-GB | 65 | 51 | 223 | 0.72 | 0.54 | 0.36 | 0.27 |
WS-X4148-RJ | 69 | 54 | 236 | 0.76 | 0.57 | 0.38 | 0.29 |
WS-X4148-RJ21 | 69 | 54 | 236 | 0.76 | 0.57 | 0.38 | 0.29 |
WS-X4412-2GB-T | 120 | 94 | 408 | 1.30 | 1.00 | 0.67 | 0.51 |
WS-X4232-L3 | 120 | 94 | 408 | 1.30 | 1.00 | 0.67 | 0.51 |
WS-X4124-FX-MT | 82 | 105 | 358 | 1.16 | 0.87 | 0.59 | 0.44 |
Two system (earth) grounding holes are provided in an enclosure near the power supplies. See Figure 2-1 for the location of the grounding holes on the Catalyst 4003 switch and Figure 2-2 for the location on the Catalyst 4006 switch.


To make an adequate grounding connection, you will need the following parts and tools:
This section describes how to connect the Catalyst 4003 and 4006 switches to earth ground. It is strongly recommended that you complete this procedure before connecting system power or turning on your switch.
To attach the grounding lug and cable to the grounding receptacle on the Catalyst 4003 and 4006 switches, perform the following steps:
Step 2 Insert the stripped end of the grounding wire into the open end of the grounding lug.
Step 3 Use the crimping tool to secure the grounding wire in place in the grounding lug.
Step 4 Locate the grounding receptacle on the switch.
See Figure 2-3 for the location of the grounding receptacle on the Catalyst 4003 switch and Figure 2-4 for the Catalyst 4006 switch.


Step 5 Remove the label that covers the grounding receptacle.
Step 6 Place the grounding lug against the grounding receptacle on the side panel of the switch.
Step 7 Insert two screws through the holes in the grounding lug and the grounding receptacle. Ensure that the grounding lug will not interfere with other switch hardware or rack equipment.
Step 8 Install the locking washers and nuts; tighten them to secure the grounding lug to the grounding receptacle.
Step 9 Prepare the other end of the grounding wire and connect it to an appropriate grounding point in your site to ensure adequate earth ground for the switch.
This section provides the guidelines for connecting Catalyst 4003 and 4006 switch AC power supplies to the site power source.
For power connection guidelines for DC-powered systems, see the "Connecting System Ground" section.
For a list of the nominal and acceptable voltage ranges for source AC power, see "Specifications."
Figure 2-5 shows the different styles of AC-input power plugs that are available for North America and various international locales.
Table 2-2 lists the AC-input power cord options and Cisco product numbers. Make sure you have the correct power cord for your site.

| Locale | Description | Product Number |
|---|---|---|
North America | 125V@13A | CAB-7KAC= |
Australia, New Zealand | 250V@10A | CAB-7KACA= |
Continental Europe | 250V@10A | CAB-7KACE= |
Italy | 250V@10A | CAB-7KACI= |
United Kingdom | 250V@10A | CAB-KACU= |
Argentina | 250V@10A | CAB-KACR= |
Table 2-3 lists the site-planning activities that you should perform before you install the Catalyst 4003 switch or the Catalyst 4006 switch. To ensure a successful switch installation, complete each activity.
| Task No. | Planning Activity | Verified By | Time | Date |
|---|---|---|---|---|
1 | Space evaluation: Space and layout |
|
|
|
2 | Environmental evaluation: Ambient temperature |
|
|
|
3 | Power evaluation: Input power type |
|
|
|
4 | Grounding evaluation: Circuit breaker size |
|
|
|
5 | Cable and interface equipment evaluation: Cable type |
|
|
|
6 | EMI evaluation: Distance limitations for signaling |
|
|
|
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Posted: Mon Jun 12 17:32:37 PDT 2000
Copyright 1989 - 2000©Cisco Systems Inc.