|
|
This chapter describes how to prepare your site for installation, as well as rack-mount the Catalyst 4908G-L3 switch router. It also provides Gigabit Interface Converter (GBIC) information and instructions for connecting power to the switch router. For first-time installations, perform the procedures in the following sections in the order listed here:
Planning the proper location and layout of your equipment rack or wiring closet is essential for successful switch router operation. Equipment placed too close together or in an inadequately ventilated area can cause system overtemperature conditions. In addition, poor equipment placement can make system panels inaccessible and difficult to maintain.
To ensure normal operation and avoid unnecessary maintenance, plan your site configuration and prepare your site before installation. For a description of the environmental monitor, see the "Power Supplies" section.
Table A-1 lists the operating and nonoperating environmental site requirements for the switch router. The environmental ranges are those within which the system continues to operate; however, a measurement that approaches the minimum or maximum of a range indicates a potential problem. You can maintain normal operation by anticipating and correcting environmental anomalies before they exceed the maximum operating range.
Verify the site power for the type of device you are installing. Power requirements are useful for planning the power distribution system needed to support the switch router. Heat dissipation is an important consideration for sizing the air-conditioning requirements for an installation. See Table A-1 for power and heat ratings for the switch router.
![]() |
Caution Verify that the total maximum load on the circuit supplying power to the power supplies is within the current ratings of the wiring and breakers to prevent a loss of input power. |
You need the following tools to install the switch router in a rack:
The following items are included in the accessory kit that ships with the chassis:
![]() |
Warning Unplug power cords before you work on a system that does not have an on/off switch. |
To install the switch router in a rack, follow these steps:
a. Place the switch router on the floor or on a sturdy table as close as possible to the rack. Leave enough clearance so that you can move around the switch router.
c. Measure the space between the inner edges of the left front and right front mounting posts to ensure that it is 17.75 inches (45.72 cm) wide.
![]() |
Note Some equipment racks provide a power strip along the length of one of the rear posts. If the rack has this feature, consider the position of the strip when planning fastener points. Before installing the L brackets on the switch router, decide whether to install the switch router from the front or the rear of the rack. |
Step 2 Remove the four (two on each side) M3 screws that are adjacent to the vent openings on the sides of the chassis. (See Figure 2-1.)
Step 3 Attach the left and right L brackets using the eight (four on each side) flat-head Phillips screws provided in the rack-mount kit. (See Figure 2-2.)
Step 4 Install the switch router in the rack as follows:
b. Align the mounting holes in the L bracket with the mounting holes in the equipment rack.
c. Secure the switch router using four (two per side) 12-24 x 3/4-inch screws through the elongated holes in the L bracket and into the threaded holes in the mounting post. (See Figure 2-3.)
The switch router powers up when you plug in the power cord. See the "Connecting Power to the Switch Router" section for instructions.
A Gigabit Interface Converter (GBIC) is a hot-swappable input/output device that plugs into the Gigabit Ethernet port, linking the switch router with the fiber-optic network. (See Figure 2-4.) The following GBIC media types are supported:
![]() |
Note Because of interoperability issues, Cisco does not support GBICs purchased from third-party vendors. See Table B-3 for GBIC port specifications. |
When using the 1000BaseLX/LH GBIC with 62.5-micron diameter multimode fiber (MMF), you must install a mode-conditioning patch cord between the GBIC and the MMF cable on both the transmit and receive ends of the link. You need the patch cord for link distances greater than 984 feet (300 meters). For link spans less than 300 meters, you can omit the patch cord.
The patch cord must comply with IEEE standards. The IEEE found that link distances did not meet with certain types of fiber-optic cable because of a problem in the center of some fiber-optic cable cores. The solution is to launch light from the laser at a precise offset from the center by using the patch cord. At the output of the patch cord, the 1000BaseLX/LH GBIC complies with the IEEE 802.3z standard for 1000BaseLX. For a detailed description of this problem, refer to the "Differential Mode Delay" section.
![]() |
Note Cisco Gigabit Ethernet products have been tested and evaluated to comply with the standards listed in "Port Pinouts." Equivalent cables should also meet these standards. |
Plug the end of the patch cord labeled "To equipment" into the GBIC (see Figure 2-5). Plug the end labeled "To cable plant" into the patch panel. The patch cord is 9.84 feet (3 meters) long and has duplex SC-type male connectors at each end.
When an unconditioned laser source (1000BaseLX/LH GBIC) designed for operation on single-mode fiber (SMF) cable is directly coupled to an MMF cable, differential mode delay (DMD) can occur. DMD can degrade the modal bandwidth of the fiber-optic cable causing a decrease in the link span (the distance between the transmitter and the receiver) that is reliably supported.
The Gigabit Ethernet specification (IEEE 802.3z) outlines parameters for Ethernet communications at a gigabits per second rate. The specification offers a higher speed version of Ethernet for backbone and server connectivity using existing deployed MMF cable. To accomplish this, the specification defines the use of laser-based optical components to propagate data over MMF cable.
Lasers function at the baud rates and longer distances required for Gigabit Ethernet. The IEEE 802.3z Gigabit Ethernet Task Force has identified the DMD condition that occurs in certain circumstances with particular combinations of lasers and MMF cable. The resulting characteristics create an additional element of "jitter" that limits the reach of Gigabit Ethernet over MMF cable.
MMF cable has only been tested for use with LED sources. LEDs create a condition within a fiber-optic cable referred to as an overfilled launch condition. The overfilled launch condition describes the way LED transmitters couple light into the fiber-optic cable in a broad spread of modes. Similar to a light bulb radiating light into a dark room, the generated light shines in multiple directions that "overfill" the existing cable space and "excites" a large number of modes (see Figure 2-6).
Lasers launch light in a more concentrated fashion. Typically, a laser transmitter couples light into only a fraction of the existing modes or optical pathways in the fiber-optic cable (see Figure 2-6).
A significant variation in the amount of DMD is produced from one MMF cable to the next. No reasonable test can be performed to survey an installed cable plant to assess the effect of DMD. Therefore, you must use the mode-conditioning patch cords for all 1000BaseLX/LH GBICs using MMF when the link span exceeds 984 feet (300 meters). For link spans less than 300 meters, you can omit the patch cord.
This section describes how to install, maintain, and remove GBICs. Read the installation information in this section before you install a GBIC.
![]() |
Caution If a 1000BaseLX/LH GBIC designed for operation on single-mode fiber (SMF) cable is directly coupled to a multimode fiber (MMF) cable, DMD can occur. See the "Differential Mode Delay" section. |
![]() |
Caution Unnecessary insertion or removal of a GBIC could lead to premature failure of the GBIC. A GBIC has a lifetime of 100 to 500 insertions or removals. |
Follow these GBIC care and handling guidelines:
The switch router ships without GBICs installed.
![]() |
Caution When inserting or removing a GBIC, always wear an ESD wrist strap connected to the ESD wrist strap connector. |
![]() |
Note GBICs are hot-swappable. |
To install a GBIC, follow these steps:
Step 2 Remove the GBIC from its protective packaging.
Step 3 Verify that the GBIC is the correct type for your network by checking the part number. The part number indicates whether it is 1000BaseSX, 1000BaseLX/LH, or 1000BaseZX.
Step 4 Grip the sides of the GBIC with your thumb and forefinger; insert the GBIC into the slot on the front of the module (see Figure 2-8).
![]() |
Note GBICs are keyed to prevent incorrect slot insertion. |
Step 5 Slide the GBIC into the slot until you hear a click. The click indicates the GBIC is locked into the slot.
Step 6 Remove the plugs from the GBIC when you are ready to attach the fiber-optic cable. Save the plugs for future use.
Step 7 If you entered the shutdown command in Step 1, enter the no shutdown command after attaching the fiber-optic cables.
![]() |
Caution Do not remove the plugs from the GBIC optical bores or the fiber-optic cable until you are ready to connect the cable. The plugs protect the GBIC optical bores and cable from contamination. |
![]() |
Note If you are removing the GBIC from an online switch router, enter the show interface command to verify the type of GBIC that is installed. |
To remove a GBIC, follow these steps:
Step 2 Disconnect the fiber-optic cable from the GBIC SC-type connector.
Step 3 Release the GBIC from the slot by simultaneously squeezing the plastic tabs (one on each side of the GBIC).
Step 4 Pull the GBIC out of the slot.
Step 5 Install the plugs in the GBIC optical bores, and place the GBIC in protective packaging.
Step 6 If you entered the shutdown command in Step 1, enter the no shutdown command after attaching the fiber-optic cables.
To connect to the Gigabit Ethernet ports, follow these steps:
Step 2 Remove the plugs from the SC-type connector on the fiber-optic cable. Insert the connector into the GBIC. (See Figure 2-9).
![]() |
Note When you plug the SC-type connector into the GBIC, make sure that both the Tx and Rx fiber-optic cables are fully inserted into the SC-type connector. |
![]() |
Note If you are using the 1000BaseLX/LH GBIC with MMF, you must install a patch cord between the GBIC and the MMF cable. See the "Patch Cord" section. |
To connect power to the switch router, follow these steps.
Step 2 Plug the power cord into the power cord connector located at the right of the back panel.
Step 3 Connect the other end of the power cord to a power source.
Step 4 Verify power supply operation by checking the front panel power supply LEDs. See Table 2-1 for LED descriptions.
See "Troubleshooting the Switch Router," if the LEDs indicate a power or other switch router problem.
To connect the switch router to a Cisco RPS, refer to the Cisco Redundant Power System Hardware Installation Guide.
The LEDs on the front panel of the switch router perform the following functions:
The status LED is located at the bottom left of the front panel. The eight Gigabit Ethernet ports are numbered 1 through 8 and have a link status LED below each port. Figure 2-10 and Figure 2-11 show the location of the LEDs on the front panel. See Table 2-1 for LED descriptions.
The PS1 and RPS LEDs are near the auxiliary and console ports at the far right of the front panel. (See Figure 2-11.)
Table 2-1 describes the LEDs.
| LED | State | Description |
|---|---|---|
Status | | The switch router performs a series of self-test diagnostics: |
Link status | Green | Operational |
PS1 | Green | Operational |
RPS | Green | Operational |
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Posted: Mon Jun 5 17:15:43 PDT 2000
Copyright 1989 - 2000©Cisco Systems Inc.