|
|
This chapter provides instructions for preparing the site for one or more Cisco 6260 digital subscriber line (DSL) access concentrators, and for unpacking, installing, and setting up the Cisco 6260.
This chapter covers the following topics. Ensure that the installation follows this sequence:
![]() | Warning For translations of the safety warnings in this chapter, see the "Translated Safety Warnings" appendix. |
This section describes requirements for the site in which the Cisco 6260 system will be installed. Before you install the Cisco 6260 system, ensure that all the criteria in this section are fully satisfied.
![]() | Warning Only trained and qualified personnel should be allowed to install or replace this equipment. |
The Cisco 6260 system connects to one or two -48 VDC inputs, plus frame ground.
A readily accessible disconnect device must be incorporated into the fixed wiring for the site.
![]() | Warning Only a DC power source that is isolated from AC mains with reinforced insulation, and that complies with the other safety extra-low voltage (SELV) requirements in UL1950, CSA 950 3rd Edition, EN 60950, and IEC950, can be connected to a Cisco 6260 system. This requirement ensures that in a catastrophic power source fault condition, hazardous voltages are not present on power terminals and connectors. |
![]() | Warning If you use wiring terminations, use only the recommended ferrules. These terminations should be the appropriate size for the wires and should clamp the conductor firmly. |
![]() | Warning
Use copper conductors only. |
The Cisco 6260 fans maintain a suitable operating temperature for the internal circuitry. Ensure that the air intake vents at the lower front of the chassis and the air exhaust vents on the top of the chassis are not obstructed in any way.
Proper operation depends upon proper environment. Cisco recommends an ambient temperature between 23° and 131° F (-5° to 55° C), and humidity between 15 percent and 90 percent noncondensing. For complete environmental requirements for the Cisco 6260, see Chapter 1.
![]() | Warning To prevent a Cisco 6260 system from overheating, do not operate it in an area that exceeds the maximum recommended ambient temperature of 131° F (55° C). |
We strongly recommend that you mount the Cisco 6260 in an equipment rack. Using hardware supplied with the chassis, the chassis can be installed in
Vertical hole spacing on the rack rails should meet standard EIA-310-C or ETS300 requirements for 1-inch (2.5 cm) spacing.
The Cisco 6260 system is shipped assembled in a cardboard box. Follow these steps when you remove the unit from the container.
![]() | Caution Static voltages as low as 30V can cause latent damage to circuitry. Be sure to observe all standard antistatic procedures when you handle this equipment. (For example, wear a grounding strap.) |
Step 1 Inspect the packing container. If any damage or other signs of mishandling are evident, inform both the carrier and Cisco before unpacking.
Step 2 Carefully remove the chassis from the container.
Step 3 Open the boxes that contain the cables and documentation. (Do not use a knife to open these boxes.)
Step 4 Before proceeding with the installation, carefully examine all assemblies, cards, and cables.
Step 5 Check the packing list to verify receipt of all components. Contact Cisco to report any discrepancies.
Install the Cisco 6260 in compliance with the following local and national electrical codes:
Review the safety warnings contained in the "Translated Safety Warnings" appendix.
Using the mounting hardware provided, mount the Cisco 6260 in a rack or cabinet.
![]() | Warning Two people are required to lift a fully configured chassis. Grasp the bottom of the chassis and lift with both hands. To prevent injury, keep your back straight and lift with your legs, not your back. To prevent damage to the chassis and components, never attempt to lift the chassis by the handles on the front of the chassis. These handles were not designed to support the weight of the chassis. |
![]() | Warning To prevent bodily injury when mounting or servicing this unit in a rack, you must take special precautions to ensure that the system remains stable. The following guidelines are provided to ensure your safety: |
Cisco provides the following mounting hardware with the Cisco 6260:
In addition, you must provide
Cisco recommends that two people perform the rack mounting procedure. If only one person is available, you will need to remove the cards, fan trays, and power entry modules (PEMs) from the chassis. Provide antistatic mats or bags to protect these components while they are outside the chassis. Also, provide a Phillips screwdriver for use in removing the components.
Follow these steps to mount a Cisco 6260 chassis in an equipment rack:
Step 1 Put on an antistatic wrist or ankle strap.
Step 2 If you are performing this procedure alone, use a Phillips screwdriver to remove the following components from the chassis so it will be light enough to lift:
Step 3 Check the ear brackets on the sides of the chassis, and if necessary reinstall them. As shown in Figure 2-1, ear brackets can be installed in two ways:
Step 4 Attach the two mounting aids to the rack, using two screws for each mounting aid. (See Figure 2-2.) The lower edge of the mounting aid lines up with the bottom of the chassis.
Step 5 Carefully lift the chassis from underneath and rest it on the mounting aids. (See Figure 2-3.)
Step 6 Push the chassis back into the rack.
Step 7 Screw the ear brackets to the rack, using two screws at the top of each ear bracket and two at the bottom (four screws per bracket). The ear brackets have both round holes and oval slots; for stability, make sure to use at least one round hole at each end of each bracket.
Step 8 If you removed components from the chassis to lighten it, replace them now.
![]() | Warning
Read the installation instructions before you connect the system to its power source. |
Connect a VT100-compatible terminal to the system console port on the NI-2 card. Connect the terminal to a power source and set it up using the values shown in Table 2-1.
![]() | Warning The ports labeled "Ethernet," "ENET," "ETH1," "ETH2," "CNSL," "AUX," and "Serial Port" are safety extra-low voltage (SELV) circuits. SELV circuits should be connected only to other SELV circuits. Because the DSL circuits are treated like telephone-network voltage circuits, avoid connecting the SELV circuit to the telephone network voltage (TNV) circuits. |
Baud rate | 9600 (transmit and receive) |
Character size | 8 bits |
Parity | None |
Stop bits | 1 |
Xon/Xoff | Hardware busy |
Follow the steps given here to connect a Cisco 6260 chassis to system ground. The system ground connection point is on the side of the chassis. Complete this procedure before you connect system power.
![]() | Warning Before connecting or disconnecting ground or power wires to the chassis, ensure that power is removed from the DC circuit. To ensure that all power is OFF, locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF position. Use a voltmeter to test for 0 (zero) voltage at the power terminals on the chassis. |
![]() | Warning
Do not work on the system or connect or disconnect cables during periods of lightning activity. |
![]() | Warning This equipment is intended to be grounded. Ensure that the host is connected to earth ground during normal use. |
Have the following items on hand before you begin the grounding procedure. Except where noted, these items are not provided with the chassis.
![]() | Warning When you are installing the unit, the ground connection must always be made first and disconnected last. |
To ensure adequate earth ground for the system, perform these steps to attach the grounding wire to the grounding receptacle on the Cisco 6260:
Step 1 Ensure that power in the DC circuit is off.
Step 2 Use a wire stripping tool to remove the covering from the end of the grounding wire. The manufacturer of the grounding lug might have a specific recommendation on the length of wire to be stripped.
Step 3 Insert the stripped end of the grounding wire into the open end of the grounding lug. Be careful not to leave any wire strands outside the lug.
Step 4 Use the crimping tool to compress the lug onto the wire.
Step 5 To verify the quality of the crimp, inspect it and tug gently on the wire.
Step 6 Locate the three grounding holes on the Cisco 6260 side panel. (See Figure 2-4.)
Step 7 Match the holes in the grounding lug to the appropriately spaced pair of grounding holes on the side of the chassis. Use the top two holes for a 5/8-inch lug, as shown in Figure 2-4. Use the bottom two holes for a 3/4-inch lug.
Step 8 Insert the screws through the holes in the lug and the chassis. Use the Phillips screwdriver to tighten the screws and secure the grounding lug firmly to the chassis.
Step 9 Prepare the other end of the grounding wire and connect it to an appropriate grounding point in your site.
This procedure tells you how to connect the Cisco 6260 system to a -48 VDC power source. Before attempting this procedure, connect the chassis to earth ground as described in the previous section.
The power connectors are receptacles in terminal blocks located on the PEMs at the lower front of the chassis (see Figure 2-8). A separate DC ground connects to the PEM as well. For full power redundancy, the power connectors on each PEM must be connected to separate power sources. If you do not require power redundancy, you can use the terminals on a single PEM, or connect both PEMs to a single power source.
![]() | Warning Only a DC power source that is isolated from AC mains with reinforced insulation, and that complies with the other safety extra-low voltage (SELV) requirements in UL1950, CSA 950 3rd Edition, EN 60950, and IEC950, can be connected to a Cisco 6260 system. This requirement assures that in a catastrophic power source fault condition, hazardous voltages are not present on power terminals and connectors. |
![]() | Warning If you use wiring terminations, use only the recommended ferrules. These terminations should be the appropriate size for the wires and should clamp the conductor firmly. |
![]() | Warning
Use copper conductors only. |
![]() | Warning Before connecting or disconnecting ground or power wires to the chassis, ensure that power is removed from the DC circuit. To ensure that all power is OFF, locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF position. Use a voltmeter to test for 0 (zero) voltage at the power terminals on the chassis. |
![]() | Warning Before working on equipment that is connected to power lines, remove jewelry (including rings, necklaces, and watches). Metal objects will heat up when connected to power and ground and can cause serious burns or become welded to the terminals. |
Have the following items on hand before you begin connecting power:
| Conductor size | 6 AWG to 10 AWG (6 AWG preferred) |
| Construction | Multistranded copper |
| Diameter | Minimum: 2.989 mm or 117.7 mil |
| Conductor Size | Order Number | Ferrule Description | Recommended Crimping Tool | |
| 10 AWG | 3200548 | AL 6-12 YE (yellow) | Crimpfox UD 6 (Order no. 1204436) |
| 8 AWG | 3200551 | AL 10-12 RD (red) | Crimpfox 25 (Order no. 1203592) |
| 6 AWG | 3200564 | AL 16-12 BU (blue) | Crimpfox 25 (Order no. 1203592) |
To prepare the power leads for the Cisco 6260, you must strip a precise amount of insulation from the end of each lead and connect the leads to their power source.
Step 1 Cut the ends of the power and ground wires so that the ends are straight, not slanted.
Step 2 Measure 0.43 inch (11 mm) up from the end of each power and ground wire and place a mark at that point. These are the wire ends that will be connected to the Cisco 6260.
Step 3 Use the wire stripping tool to remove 0.43 inch (11 mm) of the covering from the end of each wire. Trim the end of the covering so that it is straight, as shown in Figure 2-5, not slanted.
![]() | Warning Remove the covering from exactly the specified length of each power wire. If you strip too much of the covering, exposed wire protruding from the terminal block will create an electrical hazard. If you strip too little of the covering, the wire may not make a good contact with the terminal, or it may not be held securely in place in the terminal block. |
Step 4 If you are using the optional ferrules, use a crimping tool to attach them to the wires.
Step 5 Prepare the other end of each wire to be connected to a DC power source, according to the requirements of your site.
Step 6 Connect the power and ground wires to the DC power source or sources.
![]() | Warning When you are installing the unit, the ground connection must always be made first and disconnected last. |
To attach the grounding wire to the grounding receptacle on the Cisco 6260, perform these steps:
Step 1 Ensure that power in the DC circuit is off.
Step 2 Turn all three screws on the terminal block counterclockwise to open the terminal connectors. This step ensures that the correct opening is presented for the wires. See Figure 2-6.
Step 3 Insert the end of the grounding wire into the grounding receptacle, which is the bottom receptacle in the terminal block on the PEM (see Figure 2-7). If you are not using ferrules to terminate the wires, the stripped part of the wire must be fully inserted into the terminal block, so that no bare wire is exposed.
Step 4 Ensure that no wire strands are left outside the connector.
Step 5 Use the screwdriver to tighten the ground screw in the terminal block to a torque of 1.5 to 1.8 newton meters (13.28 to 15.93 inch-pounds). (Tighten in a clockwise direction.) Pull on the wire to ensure that it is held firmly in place.
Step 6 Make sure that the other end of the grounding wire is connected to ground at the DC power source.
Step 7 If you are connecting two power sources to the Cisco 6260 system, repeat this procedure for the second PEM.
![]() | Warning Only a DC power source that is isolated from AC mains with reinforced insulation, and that complies with the other safety extra-low voltage (SELV) requirements in UL1950, CSA 950 3rd Edition, EN 60950, and IEC950, can be connected to a Cisco 6260 system. This requirement ensures that in a catastrophic power source fault condition, hazardous voltages are not present on power terminals and connectors. |
![]() | Warning This unit has more than one power supply connection; all connections must be removed completely to completely remove power from the unit. |
Follow these steps to connect power to the system. Refer to Figure 2-8.
Step 1 Ensure that power in the DC circuit is off.
Step 2 Ensure that the PEMs are fully inserted into the Cisco 6260 chassis.
Step 3 Ensure that the circuit breakers on both PEMs are turned to OFF (0).
Step 4 Turn the + and - screws on the terminal block counter-clockwise to open the terminal connectors. This step ensures that the correct opening is presented for the wires. See Figure 2-6.
Step 5 Insert the battery return wire from the first external power source into the receptacle labeled + (positive) on the first PEM. The stripped part of the wire must be fully inserted, so that no bare wire is exposed. Use the screwdriver to tighten the terminal screw to a torque of 1.5 to 1.8 newton meters (13.28 to 15.93 inch-pounds). (Tighten the screws clockwise.)
![]() | Warning Wire the DC power supply as illustrated. The proper wiring sequence is ground to ground, positive to positive, and negative to negative. The ground wire must always be connected first and disconnected last. |
Step 6 Insert the power lead from the first battery -48V power source into the receptacle labeled - (negative) on the first PEM. The stripped part of the wire must be fully inserted, so that no bare wire is exposed. Use the screwdriver to tighten the terminal screw to a torque of 1.5 to 1.8 newton meters (13.28 to 15.93 inch-pounds). (Tighten the screws clockwise.)
Step 7 If you are connecting a second power source, repeat Step 5 and Step 6 to wire it to the second PEM.
Step 8 Turn on power to the DC circuit.
Step 9 Use a voltmeter to check the voltage at the terminal block. Connect the voltmeter's positive contact to the postive (+) terminal on the Cisco 6260 terminal block. Connect the voltmeter's negative contact to the negative (-) terminal on the Cisco 6260 terminal block. If the power is wired correctly, you will see a reading of +48V on the voltmeter.
Step 10 At the front of the chassis, flip the circuit breakers on both PEMs to 1 (on).
If the power is properly connected, a green LED labeled "Input OK" on the front of each PEM lights up. The green LED indicates that the PEM is making power available to the chassis. You will also hear the fans start to turn. A slight delay in fan startup is normal.
This section tells you how to connect subscriber/POTs lines, trunk lines, and, optionally, subtending lines to the Cisco 6260.
![]() | TimeSaver Cisco recommends that you label each data cable at both ends to identify its destination. |
Connect both the 10BaseT RJ-45 port on the NI-2 and the Sun SPARCstation running the CDM management application to an Ethernet so that the Cisco 6260 and the management station can communicate. Figure 2-9 shows where to connect the Ethernet cable.
![]() | Warning The ports labeled "Ethernet," "ENET," "ETH1," "ETH2," "CNSL," "AUX," and "Serial Port" are safety extra-low voltage (SELV) circuits. SELV circuits should be connected only to other SELV circuits. Because the DSL circuits are treated like telephone-network voltage circuits, avoid connecting the SELV circuit to the telephone network voltage (TNV) circuits. |
Connect a terminal, a modem, or another serial device to the RJ-45 auxiliary port on the NI-2. (This step is optional.) Figure 2-10 shows where to connect the auxiliary cable.
![]() | Warning The ports labeled "Ethernet," "ENET," "ETH1," "ETH2," "CNSL," "AUX," and "Serial Port" are safety extra-low voltage (SELV) circuits. SELV circuits should be connected only to other SELV circuits. Because the DSL circuits are treated like telephone-network voltage circuits, avoid connecting the SELV circuit to the telephone network voltage (TNV) circuits. |
Connect a DS-3 or OC-3c WAN trunk to the Cisco 6260. The OC-3c connectors are on the NI-2 card. The DS-3 connectors are on the I/O module at the top of the chassis. (If this chassis is subtended, the trunk connection goes to another Cisco 6260.) Figure 2-11 shows where to attach an OC-3c trunk cable to the NI-2 card. Figure 2-12 shows where to attach DS-3 trunk cables to the DS-3 I/O module.
Connect one subtended Cisco 6260 to the subtending interfaces on the NI-2 (OC-3c interfaces), or connect one or two subtended Cisco 6260s to the subtending interfaces on the I/O module (DS-3 interfaces). Figure 2-13 shows where to attach an OC-3c subtending cable to the NI-2 card. Figure 2-14 shows where to attach DS-3 subtending cables to the DS-3 I/O module. (Connecting subtended nodes is optional.)
Connect an external alarm device and/or a building-integrated timing source (BITS) clock to the wire wrap connector on the I/O module at the top of the chassis. (This step is optional.) See "Pin Assignments," for information on alarm relay and BITS wiring. Figure 2-15 shows the wire wrap connector on the I/O module.
Connect the RJ-21 Champ subscriber connectors at the top of the chassis to the POTS splitter (if the line is for both voice and data) or to the subscriber loop (if the line is for data only). Consult the documenation for your POTS splitter for information on its data cabling requirements. Figure 2-16 shows where to attach UTP cables to the Cisco 6260 chassis.
You have completed the hardware portion of the installation process. Cover any empty card slots with blank faceplates, and make sure the small bezel covering the air filters is in place.
![]() | Warning Blank faceplates and cover panels serve three important functions: they prevent exposure to hazardous voltages and currents inside the chassis; they contain electromagnetic interference (EMI) that might disrupt other equipment; and they direct the flow of cooling air through the chassis. Do not operate the system unless all cards, faceplates, and covers are in place. |
When you turn on the Cisco 6260 for the first time, an interactive dialog called the System Configuration Dialog appears on the console screen. The System Configuration Dialog guides you through the initial configuration process. (You can run the dialog at any time by entering the setup command in privileged EXEC mode.)
When you complete the dialog, the system displays the configuration command script that you have created. It then offers you three options:
[0] Go to the IOS command prompt without saving this config. [1] Return back to the setup without saving this config. [2] Save this configuration to nvram and exit.
If you enter 2, the configuration is saved and used. If you answer 0 or 1, the configuration you created is not saved. Enter 1 if you wish to discard the configuration and restart the System Configuration Dialog.
Take these steps before you run the System Configuration Dialog:
Step 1 Determine the IP address for the Ethernet interface.
Step 2 If you plan to configure inband management, also determine the IP address for the ATM interfaces that will be used for inband management (ATM0/1 or ATM0/2).
Step 3 Find out what the password strategy is for your environment. The System Configuration Dialog prompts you for three passwords, plus an SNMP community string. The three types of password required are enable secret, enable, and virtual terminal.
Step 4 Choose a name for the Cisco 6260. (This step is optional.)
When you power up a Cisco 6260 for the first time, you are offered the option of running the System Configuration Dialog. The System Configuration Dialog offers two configuration options: basic management setup and extended setup.
An example of the use of each option follows the "Interface Numbering" section. In each example, an arrow marks the point in the dialog where basic management setup and extended setup diverge.
The System Configuration Dialog and the command line interface use the following interface numbering scheme:
For line card interfaces, the number before the slash indicates the slot number. The number after the slash indicates the interface or port number. For example, ATM6/4 is port 4 in slot 6.
This is the basic management setup example:
--- System Configuration Dialog --- Would you like to enter the initial configuration dialog? [yes/no]: y At any point you may enter a question mark '?' for help. Use ctrl-c to abort configuration dialog at any prompt. Default settings are in square brackets '[]'. Basic management setup configures only enough connectivity for management of the system, extended setup will ask you to configure each interface on the system![]()
Would you like to enter basic management setup? [yes/no]: y Configuring global parameters: Enter host name [Router]: The enable secret is a password used to protect access to privileged EXEC and configuration modes. This password, after entered, becomes encrypted in the configuration. Enter enable secret: beansoup The enable password is used when you do not specify an enable secret password, with some older software versions, and some boot images. Enter enable password: beansoup % Please choose a password that is different from the enable secret Enter enable password: lab1 The virtual terminal password is used to protect access to the router over a network interface. Enter virtual terminal password: % No defaulting allowed Enter virtual terminal password: lab Configure SNMP Network Management? [yes]: y Community string [public]: Current interface summary Any interface listed with OK? value "NO" does not have a valid configuration Interface IP-Address OK? Method Status Protocol ATM0/0 unassigned NO unset up up Ethernet0/0 unassigned NO unset up up ATM0/1 unassigned NO unset down down ATM0/2 unassigned NO unset down down Enter interface name used to connect to the management network from the above interface summary: Ethernet0/0 Configuring interface Ethernet0/0: Configure IP on this interface? [yes]: y IP address for this interface: 172.27.144.141 Subnet mask for this interface [255.255.0.0] : Class B network is 172.27.0.0, 16 subnet bits; mask is /16 The following configuration command script was created: hostname Router enable secret 5 $1$pR/1$0zH7ohDaUKNML3SC2.RF5. enable password lab1 line vty 0 4 password lab snmp-server community public ! no ip routing ! interface ATM0/0 shutdown no ip address ! interface Ethernet0/0 no shutdown ip address 172.27.144.141 255.255.0.0 ! interface ATM0/1 shutdown no ip address ! interface ATM0/2 shutdown no ip address ! end [0] Go to the IOS command prompt without saving this config. [1] Return back to the setup without saving this config. [2] Save this configuration to nvram and exit. Enter your selection [2]: 2 % Shutdown not allowed for ATM0/0. Building configuration... Use the enabled mode 'configure' command to modify this configuration. Press RETURN to get started!
This is the extended setup example:
--- System Configuration Dialog --- Continue with configuration dialog? [yes/no]: yes At any point you may enter a question mark '?' for help. Use ctrl-c to abort configuration dialog at any prompt. Default settings are in square brackets '[]'. Basic management setup configures only enough connectivity for management of the system, extended setup will ask you to configure each interface on the system![]()
Would you like to enter basic management setup? [yes/no]: no First, would you like to see the current interface summary? [yes]: yes Interface IP-Address OK? Method Status Protocol ATM0/0 70.0.0.2 YES NVRAM up up Ethernet0/0 172.27.32.156 YES NVRAM up up ATM0/1 unassigned YES unset down down ATM0/2 unassigned YES unset administratively down down ATM18/0 unassigned YES unset initializing down ATM18/1 unassigned YES unset initializing down ATM18/2 unassigned YES unset initializing down ATM18/3 unassigned YES unset initializing down ATM21/0 unassigned YES unset administratively down down ATM21/1 unassigned YES unset administratively down down ATM21/2 unassigned YES unset administratively down down ATM21/3 unassigned YES unset administratively down down ATM26/0 unassigned YES unset down down ATM26/1 unassigned YES unset down down ATM26/2 unassigned YES unset down down ATM26/3 unassigned YES unset down down Configuring global parameters: Enter host name [Router]: sw-ni2-2 The enable secret is a password used to protect access to privileged EXEC and configuration modes. This password, after entered, becomes encrypted in the configuration. Enter enable secret: lqb The enable password is used when you do not specify an enable secret password, with some older software versions, and some boot images. Enter enable password [lab]: lab The virtual terminal password is used to protect access to the router over a network interface. Enter virtual terminal password [lab]: Configure SNMP Network Management? [no]: Configure IP? [yes]: Configure IGRP routing? [yes]: no Configuring interface parameters: Do you want to configure ATM0/0 interface? [yes]: Configure IP on this interface? [yes]: IP address for this interface [70.0.0.2]: Subnet mask for this interface [255.0.0.0] : Class A network is 70.0.0.0, 8 subnet bits; mask is /8 Do you want to configure Ethernet0/0 interface? [yes]: Configure IP on this interface? [yes]: IP address for this interface [172.27.32.156]: Subnet mask for this interface [255.255.0.0] : Class B network is 172.27.0.0, 16 subnet bits; mask is /16 Do you want to configure ATM0/1 interface? [yes]: Configure IP on this interface? [no]: Do you want to configure ATM0/2 interface? [no]: Do you want to configure ATM18/0 interface? [yes]: Configure IP on this interface? [no]: Do you want to configure ATM18/1 interface? [yes]: Configure IP on this interface? [no]: Do you want to configure ATM18/2 interface? [yes]: Configure IP on this interface? [no]: Do you want to configure ATM18/3 interface? [yes]: Configure IP on this interface? [no]: Do you want to configure ATM21/0 interface? [no]: Do you want to configure ATM21/1 interface? [no]: Do you want to configure ATM21/2 interface? [no]: Do you want to configure ATM21/3 interface? [no]: Do you want to configure ATM26/0 interface? [yes]: Configure IP on this interface? [no]: Do you want to configure ATM26/1 interface? [yes]: Configure IP on this interface? [no]: Do you want to configure ATM26/2 interface? [yes]: Configure IP on this interface? [no]: Do you want to configure ATM26/3 interface? [yes]: Configure IP on this interface? [no]: The following configuration command script was created: hostname sw-ni2-2 enable secret 5 $1$12Lo$vGKa1wlRcNyw06j1bgGQd0 enable password lab line vty 0 4 password lab no snmp-server ! ip routing ! interface ATM0/0 ip address 70.0.0.2 255.0.0.0 ! interface Ethernet0/0 ip address 172.27.32.156 255.255.0.0 ! interface ATM0/1 no ip address ! interface ATM0/2 shutdown no ip address ! interface ATM18/0 no ip address ! interface ATM18/1 no ip address ! interface ATM18/2 no ip address ! interface ATM18/3 no ip address ! interface ATM21/0 shutdown no ip address ! interface ATM21/1 shutdown no ip address ! interface ATM21/2 shutdown no ip address ! interface ATM21/3 shutdown no ip address ! interface ATM26/0 no ip address ! interface ATM26/1 no ip address ! interface ATM26/2 no ip address ! interface ATM26/3 no ip address ! end [0] Go to the IOS command prompt without saving this config. [1] Return back to the setup without saving this config. [2] Save this configuration to nvram and exit. Enter your selection [2]:2 Building configuration... Use the enabled mode 'configure' command to modify this configuration. Press RETURN to get started!
You have completed the installation process for the Cisco 6260.
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Posted: Tue Nov 23 13:40:43 PST 1999
Copyright 1989-1999©Cisco Systems Inc.