cc/td/doc/product/dsl_prod/6160
hometocprevnextglossaryfeedbacksearchhelp
PDF

Table of Contents

Installing the Cisco 6160

Installing the Cisco 6160

This chapter provides instructions for preparing the site for one or more Cisco 6160 digital subscriber line (DSL) access concentrators, and for unpacking, installing, and setting up the Cisco 6160.


Note Before you install the Cisco 6160, you might find it helpful to read "Product Overview." That chapter contains a system overview along with functional and physical descriptions of Cisco 6160 hardware components.

This chapter covers the following topics. Ensure that the installation follows this sequence:

    1. Site Preparation

    2. Unpacking and Inspection

    3. Rack-Mounting

    4. Connecting a Console Terminal

    5. Connecting System Ground

    6. Connecting System Power

    7. Making Data Connections

    8. Initial Configuration


Warning For translations of the safety warnings in this chapter, see "Translated Safety Warnings."

Site Preparation

This section describes requirements for the site in which the Cisco 6160 system will be installed. Before you install the Cisco 6160 system, ensure that all the criteria in this section are fully satisfied.


Warning Only trained and qualified personnel should be allowed to install or replace this equipment.

Power Requirements

The Cisco 6160 system connects to one or two -48 VDC inputs, plus frame ground.

A readily accessible disconnect device must be incorporated into the fixed wiring for the site.


Warning Only a DC power source that is isolated from AC mains with reinforced insulation, and that complies with the other safety extra-low voltage (SELV) requirements in UL1950, CSA 950 3rd Edition, EN 60950, and IEC950, can be connected to a Cisco 6160 system. This requirement ensures that in a catastrophic power source fault condition, hazardous voltages are not present on power terminals and connectors.


Warning Use copper conductors only.

Ventilation Requirements

The Cisco 6160 fans maintain a suitable operating temperature for the internal circuitry. Ensure that the air intake vents at the lower front of the chassis and the air exhaust vents on the top of the chassis are not obstructed in any way.

Environmental Requirements

Proper operation depends upon proper environment. Cisco recommends an ambient temperature between 41° and 104° F (5° to 40° C), and humidity between 5 percent and 90 percent noncondensing. (The system can tolerate a wider range of temperatures for short periods.) For complete environmental requirements for the Cisco 6160, see the "System Specifications and Compliances" section.


Warning To prevent a Cisco 6160 system from overheating, do not operate it in an area that exceeds the maximum recommended ambient temperature of 104° F (40° C).

Rack Requirements

We strongly recommend that you mount the Cisco 6160 in an equipment rack. Using hardware supplied with the chassis, the chassis can be installed in any ETSI 600-mm-wide (23-inch-wide) rack or cabinet.

Vertical hole spacing on the rack rails should meet standard EIA-310-C or ETS300 requirements for 1-inch (2.5 cm) spacing.

Installing Multiple Cisco 6160 Chassis in an Equipment Rack

You can install multiple Cisco 6160 chassis within a telco equipment rack. A standard seven-foot equipment rack can house four Cisco 6160 chassis, stacked one on top of another. This configuration maximizes the DSL density within a seven-foot rack. However, if space is available or if you are interested in using multiservice capabilities that the chassis will support in the future, Cisco recommends that you install no more than three Cisco 6160 chassis within a seven-foot rack. Leave a space of at least 2.5 rack units (4.375 inches, or 11.1 cm) beneath each chassis for future cable management use.

Unpacking and Inspection

The Cisco 6160 system is shipped assembled in a cardboard box. Follow these steps when you remove the unit from the container.


Caution Static voltages as low as 30V can cause latent damage to circuitry. Be sure to observe all standard antistatic procedures when you handle this equipment. (For example, wear a grounding strap.)


Step 1 Inspect the packing container. If any damage or other signs of mishandling are evident, inform both the carrier and Cisco before unpacking.

Step 2 Carefully remove the chassis from the container.

Step 3 Open the boxes that contain the cables and documentation. (Do not use a knife to open these boxes.)

Step 4 Before proceeding with the installation, carefully examine all assemblies, cards, and cables.

Step 5 Check the packing list to verify receipt of all components. Contact Cisco to report any discrepancies.


Safety

Install the Cisco 6160 in compliance with local electrical codes that apply to your site, and with the following national electrical codes:

Review the safety warnings contained in "Translated Safety Warnings."

Rack-Mounting

Using the mounting hardware provided, mount the Cisco 6160 in a rack or cabinet.


Warning Two people are required to lift a fully configured chassis. Grasp the bottom of the chassis and lift with both hands. To prevent injury, keep your back straight and lift with your legs, not your back. To prevent damage to the chassis and components, never attempt to lift the chassis by the handles on the front of the chassis. These handles were not designed to support the weight of the chassis.


Warning To prevent bodily injury when mounting or servicing this unit in a rack, you must take special precautions to ensure that the system remains stable. The following guidelines are provided to ensure your safety:
-This unit should be mounted at the bottom of the rack if it is the only unit in the rack.
-When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the heaviest component at the bottom of the rack.
-If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the unit in the rack.

Required Tools and Equipment

Cisco provides "ear" brackets with the Cisco 6160. These brackets are designed to support the weight of the chassis in the rack. The two long, L-shaped ear brackets are installed on the sides of the chassis in the factory. Each bracket is held on with four screws.

In addition, you must provide

Rack-mounting Procedure

Follow these steps to mount a Cisco 6160 chassis in an equipment rack:


Step 1 Put on an antistatic wrist or ankle strap. Connect it to the ESD jack on the front of the chassis.

Step 2 Use a Phillips screwdriver to remove the following components from the chassis so it will be light enough to lift:

Step 3 Test the weight of the chassis. If it is still too heavy for one person to lift comfortably, use the flat-blade screwdriver to remove the NI-2 and line cards.

Step 4 Check the ear brackets on the sides of the chassis, and if necessary reinstall them. Ear brackets can be installed in two ways:


Figure 2-1: Midmount Option for Ear Brackets


Step 5 Carefully lift the chassis from the bottom and place it in position in the rack.

Step 6 While your assistant holds the chassis in the rack, screw the ear brackets to the rack, using two screws at the top of each ear bracket and two at the bottom (four screws per bracket). The ear brackets have both round holes and oval slots; for stability, make sure to use at least one round hole at each end of each bracket.

Step 7 Replace all the components that you removed from the chassis to lighten it.


Caution Read the installation instructions before you connect the system to its power source.



Figure 2-2:
Front Mount Option for Ear Brackets


Connecting a Console Terminal

Connect a VT100-compatible terminal to the system console port on the NI-2 card. Connect the terminal to a power source and set it up using the values shown in Table 2-1.


Warning The ports labeled "ENET," "CNSL," and "AUX" are safety extra-low voltage (SELV) circuits. SELV circuits should be connected only to other SELV circuits. Because the DSL circuits are treated like telephone-network voltage, avoid connecting the SELV circuit to the telephone network voltage (TNV) circuits.


Table 2-1: Terminal Settings

Baud rate

9600 (transmit and receive)

Character size

8 bits

Parity

None

Stop bits

1

Xon/Xoff

Hardware busy

Connecting System Ground

Follow the steps given here to connect a Cisco 6160 chassis to system ground. The system ground connection point is on the side of the chassis. Complete this procedure before you connect system power.


Warning Before connecting or disconnecting ground or power wires to the chassis, ensure that power is removed from the DC circuit. To ensure that all power is OFF, locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF position. Use a voltmeter to test for 0 (zero) voltage at the power terminals on the chassis.


Warning Do not work on the system or connect or disconnect cables during periods of lightning activity.


Warning This equipment is intended to be grounded. Ensure that the host is connected to earth ground during normal use.

Required Tools and Equipment

Have the following items on hand before you begin the grounding procedure. Except where noted, these items are not provided with the chassis.

Connecting to System Ground


Warning When you are installing or replacing the unit, the ground connection must always be made first and disconnected last.

To ensure adequate earth ground for the system, perform these steps to attach the grounding wire to the grounding receptacle on the Cisco 6160:


Step 1 Ensure that power in the DC circuit is off.

Step 2 Use a wire stripping tool to remove the covering from the end of the grounding wire. The manufacturer of the grounding lug might have a specific recommendation on the length of wire to be stripped.

Step 3 Insert the stripped end of the grounding wire into the open end of the grounding lug. Be careful not to leave any wire strands outside the lug.

Step 4 Use the crimping tool to compress the lug onto the wire.

Step 5 To verify the quality of the crimp, inspect it and tug gently on the wire.

Step 6 Locate the three grounding holes on the Cisco 6160 side panel. (See Figure 2-3.)

Step 7 Match the holes in the grounding lug to the appropriately spaced pair of grounding holes on the side of the chassis. Use the top two holes for a 5/8-inch lug, as shown in Figure 2-3. Use the bottom two holes for a 3/4-inch lug.

Step 8 Insert the screws through the holes in the lug and the chassis. Use the Phillips screwdriver to tighten the screws and secure the grounding lug firmly to the chassis.

Step 9 Prepare the other end of the grounding wire and connect it to an appropriate grounding point in your site.



Figure 2-3:
System Ground Connection


Connecting System Power

This procedure tells you how to connect the Cisco 6160 system to a -48 VDC power source. Before attempting this procedure, connect the chassis to earth ground as described in the previous section.

The power connectors are receptacles in terminal blocks located on the back of the chassis, behind each PEM. A separate DC ground connects to each power terminal block. For full power redundancy, each terminal block must be connected to a separate power source. If you do not require power redundancy, you can wire a single terminal block, or connect both terminal blocks to a single power source.


Warning Only a DC power source that is isolated from AC mains with reinforced insulation, and that complies with the other safety extra-low voltage (SELV) requirements in UL1950, CSA 950 3rd Edition, EN 60950, and IEC950, can be connected to a Cisco 6160 system. This requirement assures that in a catastrophic power source fault condition, hazardous voltages are not present on power terminals and connectors.


Warning Use copper conductors only.


Warning Before connecting or disconnecting ground or power wires to the chassis, ensure that power is removed from the DC circuit. To ensure that all power is OFF, locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF position. Use a voltmeter to test for 0 (zero) voltage at the power terminals on the chassis.


Warning Before working on equipment that is connected to power lines, remove your jewelry (including rings, necklaces, and watches). Metal objects will heat up when connected to power and ground and can cause serious burns or become welded to the terminals.

Required Tools and Equipment

Have the following items on hand before you begin connecting power:

Conductor size

6 AWG to 8 AWG (6 AWG recommended)

Construction

Multistranded copper

Preparing to Connect Power and Ground

To prepare the power leads for the Cisco 6160, you must strip a precise amount of insulation from the end of each lead and connect the leads to their power source.


Step 1 Cut the ends of the power and ground wires so that the ends are straight, not slanted.

Step 2 Measure 1/4 inch (7 mm) up from the end of each power and ground wire and place a mark at that point. These are the wire ends that will be connected to the Cisco 6160.

Step 3 Use the wire stripping tool to remove 1/4 inch (7 mm) of the covering from the end of each wire. Trim the end of the covering so that it is straight, as shown in Figure 2-4, not slanted.


Figure 2-4: Strip and Square Off Power and Ground Wires



Warning Remove the covering from exactly the specified length of each wire. If you strip too much of the covering, exposed wire protruding from the terminal block will create an electrical hazard. If you strip too little of the covering, the wire might not make a good contact with the terminal, or it might not be held securely in place in the terminal block.

Step 4 Prepare the other end of each wire to be connected to a DC power source, according to the requirements of your site.

Step 5 Connect the power and ground wires to the DC power source or sources.


Connecting to DC Ground


Warning When you are installing the unit, the ground connection must always be made first and disconnected last.

To attach the grounding wire to the grounding receptacle on the Cisco 6160, perform these steps:


Step 1 Ensure that power in the DC circuit is off.

Step 2 Identify the correct power terminal block. There are four terminal blocks on the back of the chassis---a large one and a small one behind each PEM. (See Figure 2-5.) Use the larger terminal blocks for power and ground connections. If your system has only one PEM, you must use the large terminal block that is directly behind that PEM.


Figure 2-5: Terminal Blocks on the Back of the Cisco 6160 Chassis


Step 3 Turn all three screws on the power terminal block counterclockwise to open the terminal connectors. This step ensures that the correct opening is presented for the wires. See Figure 2-6.


Figure 2-6: Positioning the Power and Ground Terminals to Accept Wires


Step 4 Insert the end of the grounding wire into the grounding receptacle, which is the bottom receptacle in the terminal block (see Figure 2-7). The stripped part of the wire must be fully inserted into the terminal block, so that no bare wire is exposed.

Step 5 Ensure that no wire strands are left outside the connector.

Step 6 Use the screwdriver to tighten the ground screw in the terminal block to a torque of 10 inch-pounds. Eighteen inch-pounds is the destructive torque. (Tighten in a clockwise direction.) Pull on the wire to ensure that it is held firmly in place.

Step 7 Make sure that the other end of the grounding wire is connected to ground at the DC power source.

Step 8 If you are connecting two power sources to the Cisco 6160 system, repeat this procedure for the second power terminal block.


Figure 2-7: Insert Grounding Wire into Grounding Receptacle



Connecting Power to the Cisco 6160


Warning Only a DC power source that is isolated from AC mains with reinforced insulation, and that complies with the other safety extra-low voltage (SELV) requirements in UL1950, CSA 950 3rd Edition, EN 60950, and IEC950, can be connected to a Cisco 6160 system. This requirement ensures that in a catastrophic power source fault condition, hazardous voltages are not present on power terminals and connectors.


Warning This unit might have more than one power supply connection; all connections must be removed completely to completely remove power from the unit.

Follow these steps to connect power to the system. Refer to Figure 2-8.


Step 1 Ensure that power in the DC circuit is off.

Step 2 Turn the + and - screws on the terminal block counterclockwise to open the terminal connectors. This step ensures that the correct opening is presented for the wires. See Figure 2-6.

Step 3 Insert the battery return wire from the first external power source into the receptacle labeled + (positive) on the first terminal block. The stripped part of the wire must be fully inserted, so that no bare wire is exposed. Use the screwdriver to tighten the terminal screw to a torque of 10 inch-pounds. Eighteen inch-pounds is the destructive torque. (Tighten the screws clockwise.)


Warning The illustration shows the DC power supply terminal block. Wire the DC power supply as illustrated. The proper wiring sequence is ground to ground, positive to positive, and negative to negative. The ground wire must always be connected first and disconnected last.


Figure 2-8:
Connecting Power to the Terminal Block behind the PEM


Step 4 Insert the power lead from the first battery -48V power source into the receptacle labeled - (negative) on the first terminal block. The stripped part of the wire must be fully inserted, so that no bare wire is exposed. Use the screwdriver to tighten the terminal screw to a torque of 10 inch-pounds. Eighteen inch-pounds is the destructive torque. (Tighten the screws clockwise.)

Step 5 If you are connecting a second power source, repeat Step 3 and Step 4 to wire the second terminal block.

Step 6 If you want to tie down the power and ground wires, thread tie wraps through the small cutouts in the side of the chassis next to each terminal block. Then use the tie wraps to tie down the wires.

Step 7 Turn on power to the DC circuit.

Step 8 Use a voltmeter to check the voltage at the terminal block screw heads. Connect the voltmeter's positive contact to the positive (+) terminal on the Cisco 6160 terminal block. Connect the voltmeter's negative contact to the negative (-) terminal on the Cisco 6160 terminal block. If the power is wired correctly, you will see a reading of +48V on the voltmeter.

Step 9 Install the PEM(s) now if you have not done so previously.

Step 10 At the front of the chassis, flip the circuit breakers on both PEMs to 1 (on).

If the power is properly connected, a green LED labeled "Input OK" on the front of each PEM lights up. The green LED indicates that the PEM is making power available to the chassis. You will also hear the blowers start to turn. A slight delay in blower startup is normal.


Note The LED might flash red for a moment before it illuminates green. This is normal as the PEM fans speed up.


Making Data Connections

This section tells you how to connect subscriber/POTs lines, trunk lines, and, optionally, subtending lines to the Cisco 6160.


TimeSaver Cisco recommends that you label each data cable at both ends to identify its destination.

Ethernet Connection to Management Station

Connect both the 10BaseT RJ-45 port on the NI-2 and the Sun SPARC station running the CDM management application to an Ethernet so that the Cisco 6160 and the management station can communicate. Figure 2-9 shows where to connect the Ethernet cable.


Warning The ports labeled "ENET," "CNSL," and "AUX" are safety extra-low voltage (SELV) circuits. SELV circuits should be connected only to other SELV circuits. Because the DSL circuits are treated like telephone-network voltage, avoid connecting the SELV circuit to the telephone network voltage (TNV) circuits.


Figure 2-9: Ethernet Port on the NI-2 Card


Auxiliary Port Connection

Connect a terminal, a modem, or another serial device to the RJ-45 auxiliary port on the NI-2. (This step is optional.) Figure 2-10 shows where to connect the auxiliary cable.


Warning The ports labeled "ENET," "CNSL," and "AUX" are safety extra-low voltage (SELV) circuits. SELV circuits should be connected only to other SELV circuits. Because the DSL circuits are treated like telephone-network voltage, avoid connecting the SELV circuit to the telephone network voltage (TNV) circuits.


Figure 2-10:
Auxiliary Port on the NI-2 Card


Trunk Connection

Connect a DS3 or OC-3c WAN trunk to the Cisco 6160. The OC-3c connectors are on the NI-2 card. The DS3 connectors are on the I/O card on the back of the chassis. (If this chassis is subtended, the trunk connection goes to another Cisco 6160.) Figure 2-11 shows where to attach an OC-3c trunk cable to the NI-2 card. Figure 2-12 shows where to attach DS3 trunk cables to the I/O card.


Figure 2-11:
OC-3c Trunk Port on the NI-2 Card



Figure 2-12:
DS3 Trunk Port on the I/O Card


Subtending Connections

Connect one subtended Cisco 6160 to the subtending interfaces on the NI-2 (OC-3c interfaces), or connect one or two subtended Cisco 6160s to the subtending interfaces on the I/O card (DS3 interfaces). Figure 2-13 shows where to attach an OC-3c subtending cable to the NI-2 card. Figure 2-14 shows where to attach DS3 subtending cables to the I/O card. (Connecting subtended nodes is optional.)


Figure 2-13:
OC-3c Subtending Port on the NI-2 Card



Figure 2-14:
DS3 Subtending Ports on the I/O Card


Wire Wrap Connections for Alarm Relay and BITS Clock

Connect an external alarm device and/or a building-integrated timing source (BITS) clock to the wire wrap connector on the I/O card on the back of the chassis. (This step is optional.) See "Pin Assignments," for information on alarm relay and BITS wiring. Figure 2-15 shows the wire wrap connector on the I/O card.


Figure 2-15: Wire Wrap Connector on the I/O Card


Terminal Block Connections for Circuit Breaker Alarm Relay

Connect the small green terminal block behind each PEM to a visual or audible external alarm device if you want to generate an alarm when the circuit breaker on the PEM is tripped by a power fault. (This step is optional.) See "Pin Assignments," for information on circuit breaker alarm relay wiring. Figure 2-16 shows the terminal blocks for the circuit breaker alarm.


Figure 2-16:
Circuit Breaker Alarm Relay Connections on the Back of the Cisco 6160 Chassis


Subscriber/POTS Connections

Connect the eleven RJ-21 Champ subscriber connectors on the back of the chassis to the POTS splitter (if the line is for both voice and data) or to the subscriber loop (if the line is for data only). Consult the documentation for your POTS splitter for information on its data cabling requirements. Figure 2-17 shows where to attach UTP cables to the Cisco 6160 chassis.


Figure 2-17:
Subscriber Connections on the Cisco 6160 Chassis


Closing the Chassis

You have completed the hardware portion of the installation process. Cover any empty card or PEM slots with blank faceplates, and make sure the perforated bezel covering the air filter is in place.


Warning Blank faceplates and cover panels serve three important functions: they prevent exposure to hazardous voltages and currents inside the chassis; they contain electromagnetic interference (EMI) that might disrupt other equipment; and they direct the flow of cooling air through the chassis. Do not operate the system unless all cards, faceplates, and covers are in place.

Initial Configuration

When you turn on the Cisco 6160 for the first time, an interactive dialog called the System Configuration Dialog appears on the console screen. The System Configuration Dialog guides you through the initial configuration process. (You can run the dialog at any time by entering the setup command in privileged EXEC mode.)

When you complete the dialog, the system displays the configuration command script that you have created. It then offers you three options:

[0] Go to the IOS command prompt without saving this config.
[1] Return back to the setup without saving this config.
[2] Save this configuration to nvram and exit.
 

If you enter 2, the configuration is saved and used. If you answer 0 or 1, the configuration you created is not saved. Enter 1 if you wish to discard the configuration and restart the System Configuration Dialog.

Before You Begin

Take these steps before you run the System Configuration Dialog:


Step 1 Determine the IP address for the Ethernet interface.

Step 2 If you plan to configure inband management, also determine the IP address for the ATM interface that will be used for inband management (ATM0/0).

Step 3 Find out what the password strategy is for your environment. The System Configuration Dialog prompts you for three passwords, plus an SNMP community string. The three types of password required are enable secret, enable, and virtual terminal.

Step 4 Choose a name for the Cisco 6160. (This step is optional.)


Using the System Configuration Dialog

When you power up a Cisco 6160 for the first time, you are offered the option of running the System Configuration Dialog. The System Configuration Dialog offers two configuration options: basic management setup and extended setup.

An example of the use of each option follows the "Interface Numbering" section, below. In each example, an arrow marks the point in the dialog where basic management setup and extended setup diverge.

Interface Numbering

The System Configuration Dialog and the command line interface use the following interface numbering scheme:

For line card interfaces, the number before the slash indicates the slot number. The number after the slash indicates the interface or port number. For example, ATM6/4 is port 4 in slot 6.

Basic Management Setup Example

This is the basic management setup example:

         --- System Configuration Dialog ---
 
Would you like to enter the initial configuration dialog? [yes/no]: y
At any point you may enter a question mark '?' for help.
Use ctrl-c to abort configuration dialog at any prompt.
Default settings are in square brackets '[]'.
 
Basic management setup configures only enough connectivity
for management of the system, extended setup will ask you
to configure each interface on the system
 
Would you like to enter basic management setup? [yes/no]: y
 
Configuring global parameters:
 
  Enter host name [DSLAM]:
 
  The enable secret is a password used to protect access to
  privileged EXEC and configuration modes. This password, after
  entered, becomes encrypted in the configuration.
  Enter enable secret: beansoup
 
  The enable password is used when you do not specify an
  enable secret password, with some older software versions, and
  some boot images.
  Enter enable password: beansoup
% Please choose a password that is different from the enable secret
  Enter enable password: lab1
 
  The virtual terminal password is used to protect
  access to the router over a network interface.
  Enter virtual terminal password: 
% No defaulting allowed
  Enter virtual terminal password: lab
 
  Configure SNMP Network Management? [yes]: y
    Community string [public]: 
 
 
Current interface summary
 
Any interface listed with OK? value "NO" does not have a valid configuration
 
Interface             IP-Address      OK? Method Status                Protocol
ATM0/0                unassigned      NO  unset  up                    up      
Ethernet0/0           unassigned      NO  unset  up                    up      
ATM0/1                unassigned      NO  unset  down                  down    
ATM0/2                unassigned      NO  unset  down                  down    
 
Enter interface name used to connect to the
management network from the above interface summary: Ethernet0/0
 
Configuring interface Ethernet0/0:
  Configure IP on this interface? [yes]: y
    IP address for this interface: 172.27.144.141
    Subnet mask for this interface [255.255.0.0] : 
    Class B network is 172.27.0.0, 16 subnet bits; mask is /16
 
The following configuration command script was created:
 
hostname DSLAM
enable secret 5 $1$pR/1$0zH7ohDaUKNML3SC2.RF5.
enable password lab1
line vty 0 4
password lab
snmp-server community public
!
no ip routing
 
!
interface ATM0/0
no ip address
!
interface Ethernet0/0
no shutdown
ip address 172.27.144.141 255.255.0.0
!
interface ATM0/1
shutdown
no ip address
!
interface ATM0/2
shutdown
no ip address
!
end
 
 
[0] Go to the IOS command prompt without saving this config.
[1] Return back to the setup without saving this config.
[2] Save this configuration to nvram and exit.
 
Enter your selection [2]: 2
% Shutdown not allowed for ATM0/0.
Building configuration...
Use the enabled mode 'configure' command to modify this configuration.
 
 
Press RETURN to get started!
 
 

Extended Setup Example

This is the extended setup example:

         --- System Configuration Dialog ---
 
Continue with configuration dialog? [yes/no]: yes
 
At any point you may enter a question mark '?' for help.
Use ctrl-c to abort configuration dialog at any prompt.
Default settings are in square brackets '[]'.
 
 
Basic management setup configures only enough connectivity
for management of the system, extended setup will ask you
to configure each interface on the system
 
Would you like to enter basic management setup? [yes/no]: no
 
First, would you like to see the current interface summary? [yes]: yes
 
Interface              IP-Address      OK? Method Status                Protocol
ATM0/0                 70.0.0.2        YES NVRAM  up                    up      
Ethernet0/0            172.27.32.156   YES NVRAM  up                    up      
ATM0/1                 unassigned      YES unset  down                  down    
ATM0/2                 unassigned      YES unset  administratively down down    
ATM18/0                unassigned      YES unset  initializing          down    
ATM18/1                unassigned      YES unset  initializing          down    
ATM18/2                unassigned      YES unset  initializing          down    
ATM18/3                unassigned      YES unset  initializing          down    
ATM21/0                unassigned      YES unset  administratively down down    
ATM21/1                unassigned      YES unset  administratively down down    
ATM21/2                unassigned      YES unset  administratively down down    
ATM21/3                unassigned      YES unset  administratively down down    
ATM26/0                unassigned      YES unset  down                  down    
ATM26/1                unassigned      YES unset  down                  down    
ATM26/2                unassigned      YES unset  down                  down    
ATM26/3                unassigned      YES unset  down                  down    
 
Configuring global parameters:
 
  Enter host name [DSLAM]: sw-ni2-2
 
  The enable secret is a password used to protect access to
  privileged EXEC and configuration modes. This password, after
  entered, becomes encrypted in the configuration.
  Enter enable secret: lqb
 
  The enable password is used when you do not specify an
  enable secret password, with some older software versions, and
  some boot images.
  Enter enable password [lab]: lab
 
  The virtual terminal password is used to protect
  access to the router over a network interface.
  Enter virtual terminal password [lab]:
  Configure SNMP Network Management? [no]:
  Configure IP? [yes]:
    Configure IGRP routing? [yes]: no
 
Configuring interface parameters:
 
Do you want to configure ATM0/0  interface? [yes]:
  Configure IP on this interface? [yes]:
    IP address for this interface [70.0.0.2]:
    Subnet mask for this interface [255.0.0.0] :
    Class A network is 70.0.0.0, 8 subnet bits; mask is /8
 
Do you want to configure Ethernet0/0  interface? [yes]:
  Configure IP on this interface? [yes]:
    IP address for this interface [172.27.32.156]:
    Subnet mask for this interface [255.255.0.0] :
    Class B network is 172.27.0.0, 16 subnet bits; mask is /16
 
Do you want to configure ATM0/1  interface? [yes]:
  Configure IP on this interface? [no]:
 
Do you want to configure ATM0/2  interface? [no]:
 
Do you want to configure ATM18/0  interface? [yes]:
  Configure IP on this interface? [no]:
 
Do you want to configure ATM18/1  interface? [yes]:
  Configure IP on this interface? [no]:
 
Do you want to configure ATM18/2  interface? [yes]:
  Configure IP on this interface? [no]:
 
Do you want to configure ATM18/3  interface? [yes]:
  Configure IP on this interface? [no]:
 
Do you want to configure ATM21/0  interface? [no]:
 
Do you want to configure ATM21/1  interface? [no]:
 
Do you want to configure ATM21/2  interface? [no]:
 
Do you want to configure ATM21/3  interface? [no]:
 
Do you want to configure ATM26/0  interface? [yes]:
  Configure IP on this interface? [no]:
 
Do you want to configure ATM26/1  interface? [yes]:
  Configure IP on this interface? [no]:
 
Do you want to configure ATM26/2  interface? [yes]:
  Configure IP on this interface? [no]:
 
Do you want to configure ATM26/3  interface? [yes]:
  Configure IP on this interface? [no]:
 
The following configuration command script was created:
 
hostname sw-ni2-2
enable secret 5 $1$12Lo$vGKa1wlRcNyw06j1bgGQd0
enable password lab
line vty 0 4
password lab
no snmp-server
!
ip routing
!
interface ATM0/0
ip address 70.0.0.2 255.0.0.0
!
interface Ethernet0/0
ip address 172.27.32.156 255.255.0.0
!
interface ATM0/1
no ip address
!
interface ATM0/2
shutdown
no ip address
!
interface ATM18/0
no ip address
!
interface ATM18/1
no ip address
!
interface ATM18/2
no ip address
!
interface ATM18/3
no ip address
!
interface ATM21/0
shutdown
no ip address
!
interface ATM21/1
shutdown
no ip address
!
interface ATM21/2
shutdown  
no ip address
!
interface ATM21/3
shutdown
no ip address
!
interface ATM26/0
no ip address
!
interface ATM26/1
no ip address
!
interface ATM26/2
no ip address
!
interface ATM26/3
no ip address
!
end
 
 
[0] Go to the IOS command prompt without saving this config.
[1] Return back to the setup without saving this config.
[2] Save this configuration to nvram and exit.
 
Enter your selection [2]:2
Building configuration...
Use the enabled mode 'configure' command to modify this configuration.
 
 
Press RETURN to get started!
 

You have completed the installation process for the Cisco 6160.


hometocprevnextglossaryfeedbacksearchhelp
Posted: Thu Jul 6 14:52:48 PDT 2000
Copyright 1989-2000©Cisco Systems Inc.