| Equipment Item | Vertical Rack Units (1 VRU = 1.75 in.) |
Reserved for Customer Provided Power | 6 VRU |
120 Ohm Patch Panel | 3 VRU |
Ethernet Hub | 1 VRU |
Failover Control Box | 5 VRU |
Barrier Strip | 2 VRU |
ARU | 1 VRU |
Serial Port Expander | 2 VRU |
Sun 450 | 14 VRU |
Empty Space | 7 VRU |


| CABLE ID | END A CONNECTOR TYPE | CONNECTS TO | CABLE TYPE | END B CONNECTOR TYPE | CONNECTS TO |
|---|---|---|---|---|---|
COM1 | RJ45 | Port COM of the RJ45 card in slot #1 of the Failover Controller | CAT5 | Wire wrap | Terminated on the DSX Patch Panel position 1B |
COM2 | RJ45 | Port COM of the RJ45 card in slot #2 of the Failover Controller | CAT5 | Wire wrap | Terminated on the DSX Patch Panel position 2B |
1A | RJ45 | Port A of the RJ45 card in slot #1 of the Failover Controller | CAT5 | RJ45 | Terminated on ITK card in slot #1 of SUN A |
2A | RJ45 | Port A of the RJ45 card in slot #2 of the Failover Controller | CAT5 | RJ45 | Terminated on ITK card in slot #2 of SUN A |
1B | RJ45 | Port B of the RJ45 card in slot #1 of the Failover Controller | CAT5 | RJ45 | Terminated on ITK card in slot #1 of SUN B |
2B | RJ45 | Port B of the RJ45 card in slot #2 of the Failover Controller | CAT5 | RJ45 | Terminated on ITK card in slot #2 of SUN B |
A-ALM-MON-1 | RJ45 | Port MON of the ARU #1 | CAT5 | RJ45 with RS232 adapter | Port #2 of the Serial Port Expander #1 |
B-ALM-MON-1 | RJ45 | Port MON of the ARU #2 | CAT5 | RJ45 with RS232 adapter | Port #2 of the Serial Port Expander #2 |
A-ALM-REL-1 | DB15 | RELAYS port of the ARU #1 | 16 gauge conductor | Spade Connectors | Terminated on the barrier strip |
B-ALM-REL-2 | DB15 | RELAYS port of the ARU #2 | 16 gauge conductor | Spade Connectors | Terminated on the barrier strip |
A-FC-1 | DB25-male | Port A of the control card in slot #1 of the Failover Controller | RS232 | DB25-male | Port #1 of the Serial Port Expander #1 |
B-FC-1 | DB25-male | Port B of the control card in slot #1 of the Failover Controller | RS232 | DB25-male | Port #1 of the Serial Port Expander #2 |
HB-0 | DB25-male | Port 0 of Serial Port Expander #1 | RS232 | DB25-male with null modem adapter | Port 0 of Serial Port Expander #2 |
LAN | RJ45 | LAN connection of Sun A | LAN cable | RJ45 | Ethernet Hub |
LAN | RJ45 | LAN connection of Sun B | LAN cable | RJ45 | Ethernet Hub |
This is a color code document, referring to the cables in the TransPath System for the failover, alarm, and Ethernet connectivity.
Pin 1 | white/orange |
Pin 2 | orange/white |
Pin 3 | white/green |
Pin 4 | blue/white |
Pin 5 | white/green |
Pin 6 | green/white |
Pin 7 | white/brown |
Pin 8 | brown/white |
This is for the connection of the ARU to the barrier strip.
| PIN # | CIRCUIT | DESIGNATION | PIN # | COLOR PAIR |
|---|---|---|---|---|
8 | #1 | Normally Closed | 1 | black/brown |
15 | #1 | Common | 2 | brown/black |
7 | #1 | Normally Open | 3 | black/orange |
14 |
| No Connection | 4 | orange/black |
6 | #2 | Normally Closed | 5 | black/white |
13 | #2 | Common | 6 | white/black |
5 | #2 | Normally Open | 7 | black/green |
12 |
| No Connection | 8 | green/black |
4 | #3 | Normally Closed | 9 | black/blue |
11 | #3 | Common | 10 | blue/black |
3 | #3 | Normally Open | 11 | black/yellow |
10 |
| No Connection | 12 | yellow/black |
2 | #4 | Normally Closed | 13 | black/red |
9 | #4 | Common | 14 | red/black |
1 | #4 | Normally Open | 15 | white/red |
| Note red is not used | ||||
This cable goes from the ITK card in the Sun machine to the DSX Patch Panel
Pin 1 | white/blue |
Pin 2 | blue/white |
Pin 3 | spare |
Pin 4 | white/orange |
Pin 5 | orange/white |
Pin 6 | spare |
Pin 7 | spare |
Pin 8 | spare |
The lower position wire wrap Patch Panel Wiring List matrix allows inbound and outbound E1 facilities to be given appearances at specified patch positions. The following assignments are to be made for the E1s used by TransPath.
| Location | Facility | |
|---|---|---|
| Ckt Group/Column | Terminal | Assignment |
A/1 | IN/T | E1-NET-1 IN+ |
A/1 | IN/R | E1-NET-1 IN- |
A/1 | OUT/T | E1-NET-1 OUT+ |
A/1 | OUT/R | E1-NET-1 OUT- |
A/2 | IN/T | E1-NET-2 IN+ |
A/2 | IN/R | E1-NET-2 IN- |
A/2 | OUT/T | E1-NET-2 OUT+ |
A/2 | OUT/R | E1-NET-2 OUT- |
B/1 | IN/T | AB-RJ45-1 IN+ |
B/1 | IN/R | AB-RJ45-1 IN- |
B/1 | OUT/T | AB-RJ45-1 OUT+ |
B/1 | OUT/R | AB-RJ45-1 OUT- |
B/2 | IN/T | AB-RJ45-2 IN+ |
B/2 | IN/R | AB-RJ45-2 IN- |
B/2 | OUT/T | AB-RJ45-2 OUT+ |
B/2 | OUT/R | AB-RJ45-2 OUT- |
The upper position wire wrap matrix allows 'normal through' interconnections to be made for specified patch positions. The following table describes the wiring necessary to support E1s and associated trace indicator LEDs.
| From | To | ||
|---|---|---|---|
| Ckt Group/Column | Terminal | Ckt Group/Column | Terminal |
A/1 | IN/TN | B/1 | OUT/TN |
A/1 | IN/RN | B/1 | OUT/RN |
A/1 | TL | B/1 | TL |
A/1 | LG | B/1 | LG |
A/1 | OUT/TN | B/1 | IN/TN |
A/1 | OUT/RN | B/1 | IN/RN |
A/2 | IN/TN | B/2 | OUT/TN |
A/2 | IN/RN | B/2 | OUT/RN |
A/2 | TL | B/2 | TL |
A/2 | LG | B/2 | LG |
A/2 | OUT/TN | B/2 | IN/TN |
A/2 | OUT/RN | B/2 | IN/RN |
For example, a single "A" side E1 facility has one pair wired to the lower left hand terminals while the other pair is wired to the lower right hand terminals, whilst "normal through" wiring is always upper left to upper right.

|
|