The key to troubleshooting is to isolate the problem to a specific subsystem. Start by reading the LEDs on the front panel of the Cisco RPS and any error messages displayed on the external device console. If you are unable to resolve the problem, refer to the "Getting Technical Support" section.
This chapter contains the following sections:
The LEDs on the front panel of the Cisco RPS (see Figure 5-1) display the current operating condition of the RPS. Refer to Table 1-2 for the meaning of various LED colors. When the Cisco RPS is working properly, the LEDs are solid green. When there is a problem with any component, the related LED is amber.
Table 5-1 lists symptoms indicating a problem, along with possible causes and suggested corrective actions.

| Symptom | Description of Error | Corrective Action | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
DC LED 1, 2, 3, or 4 is amber. Note The DC LED is always amber for 10 to 15 seconds after the DC output module has been connected and the external device has been powered on. | The cable connected to an internal DC output module is loose, or the internal DC output module has failed. Note If you are using an RPS with a revision level lower than Z3 with a Catalyst 3508G or a Catalyst 3548 XL switch, the switch RPS LED and the RPS DC LED of the connector to the switch might display amber (normally indicating an RPS malfunction) even when the RPS is functioning properly. The LEDs display correctly for RPS revision level Z3 or later. The label on the bottom of the RPS shows the revision level. | The DC status LED numbers correspond to the DC output connectors on the Cisco RPS rear panel. Check the LEDs to determine which connector is affected. Note The following steps power down the external device if it is not already down.
If the failure persists, the DC output module has failed, and the Cisco RPS needs to be replaced. If there is an unused DC output module, try switching to it as a temporary solution. | ||||||||||
AC 1 or 2 LED is amber or off. | One of the following has occurred:
| Look at the AC LEDs to determine which AC module is reporting the error.
If the failure persists, one of the AC output modules has failed, and the Cisco RPS needs to be replaced. Contact your Cisco representative or reseller.
| ||||||||||
FAN LED is amber. | One of the fans has failed. The remaining fans switch to full speed to keep the Cisco RPS cool.
| The Cisco RPS continues to operate with a single fan failure. To correct the failure, replace the Cisco RPS. Contact your Cisco representative or reseller.
| ||||||||||
TEMP LED is amber. | The temperature inside the Cisco RPS is too high.
|
If the LED remains amber, replace the Cisco RPS. Contact your Cisco representative or reseller.
|
Cisco IOS Release 11.2(7)P and later releases support status messages for Cisco 3620/3640 series routers using the Cisco RPS. Cisco IOS Release 11.3(2) and later releases support status messages for Cisco 2600 series routers using the Cisco RPS.
Status messages are not supported for the FastHub 400 series hubs, Cisco 1516M hubs (HP 10BaseT Hub-16M), Catalyst 1900 and Catalyst 2820 series switches, Catalyst 2900 and 3500 series XL switches, Cisco 2500 and 4000 series routers, and the Cisco MC3810 multiservice concentrator.
The show env command (available in Cisco IOS Releases 11.2(7) and later releases) provides an environmental status of the Cisco RPS. An example display follows:
router# show env Power Supply: Redundant Power supply is present. Thermal status is normal. AC status is normal. DC status is normal. Board Temperature: Warning: Board overtemperature condition detected.
![]() | Caution If the Cisco RPS gets too hot, it shuts down to prevent damage to its components. If thermal shutdown occurs because the cooling system failed or the ambient temperature rose above normal operating limits, a thermal warning displays on the router console, and an SNMP trap is sent before shutdown. |
When a Cisco RPS status failure is detected while connected to Cisco 2600 and 3620/3640 series routers, Cisco IOS software receives an interrupt and displays the error messages on the router console. The following sections describe the console messages and SNMP traps issued following each error condition and after corrective action.
LED status: DC LED 1, 2, 3, or 4 is amber.
Console Error Message:
System detected Redundant Power Supply DC FAIL condition.
*** System Environmental Interrupt ***WARNING: REDUNDANT POWER SUPPLY DC FAIL BIT IS ASSERTED.
Error Description:
The cable connected to one of the internal DC output modules is loose, or one of the internal DC output modules in the Cisco RPS has failed.
SNMP Trap Issued Upon Error:
ciscoEnvMonRedundantSupplyNotification is generated.
The varbinds included are ciscoEnvMonSupplyStatusDescr and ciscoEnvMonSupplyState.
The value of ciscoEnvMonSupplyState is a warning.
How to Correct Error:
Check the DC LEDs on the front panel of the Cisco RPS to determine which cable is loose or if the module has failed, and try the corrective actions described in Table 5-1.
Console Message Issued Upon Correction of Error:
Redundant Power Supply DC condition is now normal.
SNMP Trap Issued Upon Correction of Error:
ciscoEnvMonRedundantSupplyNotification is generated.
The varbinds included are ciscoEnvMonSupplyStatusDescr and ciscoEnvMonSupplyState.
The value of ciscoEnvMonSupplyState is normal.
LED status: AC LED 1 or 2 is amber or off.
Console Error Message:
System detected Redundant Power Supply AC FAIL condition.
*** System Environmental Interrupt ***WARNING: REDUNDANT POWER SUPPLY AC FAIL BIT IS ASSERTED.
Error Description:
One of the AC modules has been turned off or has been disconnected or has failed. See Table 5-1 for details. The Cisco IOS software checks the condition every 30 seconds. If the condition still exists, the error message redisplays.
SNMP Trap Issued Upon Error:
ciscoEnvMonRedundantSupplyNotification is generated.
The varbinds included are ciscoEnvMonSupplyStatusDescr and ciscoEnvMonSupplyState.
The value of ciscoEnvMonSupplyState is a warning.
How to Correct Error:
Check the AC LEDs on the Cisco RPS to determine which AC module is reporting the error, and try the corrective actions described in Table 5-1.
Console Message Issued Upon Correction of Error:
Redundant Power Supply AC condition is now normal.
SNMP Trap Issued Upon Correction of Error:
ciscoEnvMonRedundantSupplyNotification is generated.
The varbinds included are ciscoEnvMonSupplyStatusDescr and ciscoEnvMonSupplyState.
The value of ciscoEnvMonSupplyState is normal.
LED status: FAN LED is amber.
Console Error Message:
System detected Redundant Power Supply THERMAL FAIL condition.
*** System Environmental Interrupt ***WARNING: REDUNDANT POWER SUPPLY THERMAL BIT IS ASSERTED.
Error Description:
One of the Cisco RPS fans has failed. The remaining fans switch to full speed to keep the Cisco RPS cool.
SNMP Trap Issued Upon Error:
ciscoEnvMonRedundantSupplyNotification is generated.
The varbinds included are ciscoEnvMonSupplyStatusDescr and ciscoEnvMonSupplyState.
The value of ciscoEnvMonSupplyState is a warning.
How to Correct Error:
The Cisco RPS continues to operate with a single fan failure, but to correct the failure, replace the Cisco RPS.
Console Message Issued Upon Correction of Error:
Redundant Power Supply THERMAL condition is now normal.
SNMP Trap Issued Upon Correction of Error:
ciscoEnvMonRedundantSupplyNotification is generated.
The varbinds included are ciscoEnvMonSupplyStatusDescr and ciscoEnvMonSupplyState.
The value of ciscoEnvMonSupplyState is normal.
LED status: TEMP LED is amber.
Console Error Message:
System detected Redundant Power Supply THERMAL FAIL condition.
*** System Environmental Interrupt ***WARNING: REDUNDANT POWER SUPPLY THERMAL BIT IS ASSERTED.
Error Description:
The temperature inside the Cisco RPS is too hot.
SNMP Trap Issued Upon Error:
ciscoEnvMonRedundantSupplyNotification is generated.
The varbinds included are ciscoEnvMonSupplyStatusDescr and ciscoEnvMonSupplyState.
The value of ciscoEnvMonSupplyState is a warning.
How to Correct Error:
Console Message Issued Upon Correction of Error:
Redundant Power Supply THERMAL condition is now normal
SNMP Trap Issued Upon Correction of Error:
ciscoEnvMonRedundantSupplyNotification is generated.
The varbinds included are ciscoEnvMonSupplyStatusDescr and ciscoEnvMonSupplyState.
The value of ciscoEnvMonSupplyState is normal.
LED status: Two or more of the Cisco RPS LEDs are amber.
Console Error Message:
There is more than one failure with the redundant power systems; please resolve problems immediately.
The message will vary depending on the mix of failures.
Error Description:
The Cisco RPS has two or more failures of any of the previous types.
SNMP Trap Issued Upon Error:
ciscoEnvMonRedundantSupplyNotification is generated.
The varbinds included are ciscoEnvMonSupplyStatusDescr and ciscoEnvMonSupplyState.
The value of ciscoEnvMonSupplyState is critical.
How to Correct Error:
Look at the LEDs on the Cisco RPS front panel to determine the types of failures that have occurred. Go to the section in Table 5-1 describing each failure type for instructions on how to correct it.
If the error message persists, replace the Cisco RPS.
Console Message Issued Upon Correction of Error:
Redundant power system is now normal.
SNMP Trap Issued Upon Correction of Error:
ciscoEnvMonRedundantSupplyNotification is generated.
The varbinds included are ciscoEnvMonSupplyStatusDescr and ciscoEnvMonSupplyState.
The value of ciscoEnvMonSupplyState is normal.
Step 1 Power down the external device.
(a) If the external device is a router or concentrator, press the on/off switch to the off position.
(b) If the external device is a hub or switch configured in redundant-with-reboot mode, disconnect the AC power cord. (If the hub or switch is in quasi-redundant mode, step 2 powers down the switch.)
Step 2 Disconnect the Cisco RPS connector from the external device. Make sure to leave the AC input power cable connected to the RPS.
Step 3 Replace the failed external device.
Step 4 If the external device is a hub or switch in redundant-with-reboot mode, connect the external device AC power cord to an AC power outlet to turn on power.
Step 5 Reconnect the new external device to the Cisco RPS power cable.
Step 6 If the external device is a router or concentrator, press the device on/off switch to the on (|) position to power up the device.
The new external device powers up in 10 to 15 seconds.
If you cannot locate the source of the problem, refer to the information packet publication that shipped with your Cisco RPS for information about how to contact technical support. Before you contact technical support, have the following information ready:
If the product is under warranty or is covered by a Cisco maintenance contract, contact Cisco's Technical Assistance Center (TAC) at 800 533-2447, 408 526-7209, tac@cisco.com, or http://www.cisco.com.
![]()
![]()
![]()
![]()
![]()
![]()
![]()